7.10 Troubleshooting Without Fault Display
308
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
7.10
Troubleshooting Without Fault Display
If the drive or motor operate incorrectly, but the keypad does not show a fault or error code, refer to the items in
this section.
•
Motor hunting and oscillation
•
Unsatisfactory motor torque
•
Unsatisfactory speed precision
•
Unsatisfactory motor torque and speed response
•
Motor noise
◆
The Parameter Settings Will Not Change
Causes
Possible Solutions
The drive is operating the motor (the drive is in Drive Mode).
Stop the drive and change to Programming Mode.
Parameter
A1-01 = 0 [Access Level = Monitor only]
.
Set
A1-01 = 2 [Standard Parameters]
or
A1-01 = 3 [Expert Parameters]
.
Parameter
H1-xx: MFDI Function Select = 7C [Prg Lock]
.
Turn ON the terminals to which
H1-xx = 7C
is set, and then change the parameters.
An incorrect password was entered in
A1-04 [Password Input]
.
•
Enter the correct password to
A1-04
again.
•
If you forgot the password, set the password again with
A1-04
and
A1-05 [Password Setting]
.
Note:
If the password is set, it will not be possible to change these parameters until the password
matches:
•
A1-01 [Access Level]
•
A1-02 [Control Method]
•
A1-03 [Init Parameters]
•
A1-06 [Macro Preset]
•
A1-07 [Q2pack Enable]
•
A2-01 to A2-32 [MAN1 Param1 to MAN3 Param12]
The drive detected
Uv [Undervoltage]
.
•
View
U1-07 [DC Bus Voltage]
to see the power supply voltage.
•
Examine the main circuit wiring.
◆
The Motor Does Not Rotate After Entering Run Command
Causes
Possible Solutions
The drive is not in Drive Mode.
1.
Make sure that the keypad shows [Rdy].
2.
If the keypad does not show [Rdy], go back to the Home screen.
The drive stopped,
was pushed, and changed the Run command
source to the keypad.
Do one of these two:
•
Push
.
•
Re-energize the drive.
Note:
Set
o2-01 = 0 [LO/RE Key Selection of Function = Disabled]
to prevent changing the Run
command source with
.
Auto-Tuning completed.
Go back to the Home screen on the keypad.
Note:
When Auto-Tuning completes, the drive changes to Programming Mode. The drive will not
accept a Run command unless the drive is in Drive Mode.
The drive received a fast stop command.
Turn off the fast stop input signal.
The settings for the source that supplies the Run command are incorrect.
Set
b1-02 [Run Comm. Sel 1]
correctly.
The frequency reference source is set incorrectly.
Set
b1-01 [Freq. Ref. Sel. 1]
correctly.
There is defective wiring in the control circuit terminals.
•
Correctly wire the drive control circuit terminals.
•
View
U1-10 [In Terminal Status]
for input terminal status.
The settings for voltage input and current input of the master frequency
reference are incorrect.
Examine these analog input terminal signal level settings:
•
Terminal AI1: DIP switch S1-1 and
H3-01 [AI1 Signal Level Select]
•
Terminal AI2: DIP switch S1-2 and
H3-09 [AI2 Signal Level Select]
•
Terminal AI3: DIP switch S4, S1-3 and
H3-05 [AI3 Signal Level Select]
The selection for the sinking/sourcing mode and the internal/external power
supply is incorrect.
•
For sinking mode, close the circuit between terminals DIC-D24V with a wire jumper.
•
For sourcing mode, close the circuit between terminals DIC-DI0V with a wire jumper.
•
For external power supply, remove the wire jumper.
The frequency reference is too low.
•
View
U1-01 [Frequency Reference]
.
•
Increase the frequency reference to a value higher than
E1-09 [Min Output Frequency]
.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...