SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
■
E5-01 PM Mot Code Selection
No.
(Hex.)
Name
Description
Default
(Range)
E5-01
(0329)
PM Mot Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to set some
parameters to their correct settings automatically.
Determined by A1-02, o2-
04, and C6-01
(0000 - FFFF)
Note:
•
If the drive hunts or shows an alarm after you use a motor code, use the keypad to enter the value shown on the nameplate to
E5-xx
.
•
When you use a PM motor other than a Yaskawa SMRA, SSR1, or SST4 series, set
E5-01 = FFFF
.
gives information about the motor code setting digits.
Figure 12.69 PM Motor Code
■
E5-02 PM Mot Rated Power (kW)
No.
(Hex.)
Name
Description
Default
(Range)
E5-02
(032A)
PM Mot Rated Power (kW)
Sets the PM motor rated output in the units from
o1-58 [Mot Capacity Unit]
.
Determined by E5-01
(0.10 - 650.00 kW)
These types of Auto-Tuning will automatically set this parameter:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM Rotational Auto-Tuning
■
E5-03 PM Mot Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E5-03
(032B)
PM Mot Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by E5-01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: 4002 to 4023
•
0.1 A: 4031 to 4675
The drive automatically sets
E5-03
to the value input for
“
PM Motor Rated Current
”
after you do these types of
Auto-Tuning:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM StaTun for Stator Resistance
•
PM Rotational Auto-Tuning
■
E5-04 PM Mot Pole Count
No.
(Hex.)
Name
Description
Default
(Range)
E5-04
(032C)
PM Mot Pole Count
Sets the number of PM motor poles.
Determined by E5-01
(2 - 120)
Note:
•
When
A1-02 = 7 [Control Method = PM CLVector]
, the maximum value is 120.
•
When
A1-02 = 5, 6 or 8 [PM OLVector, PM AOLVector or EZ Vector]
, the maximum value is 48.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...