SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
767
Figure 12.123 Cancel KEB Operation without Using the KEB Ride-Thru if Restoration of Power Occurs while the
Control Power (Power Supply to the Control Board) is Maintained
*1
When setting
L2-07 = 0.00
, the drive reaccelerates in accordance with the valid
Acceleration Time [C1-01,
C1-03, C1-05, C1-07]
, and normal operation resumes.
Use the KEB Ride-Thru to Cancel KEB Operation when Restoration of Power Occurs while the Control
Power (Power Supply to the Control Board) is Maintained
shows an example with this configuration:
•
L2-01 = 4
.
•
Use
KEB Ride-Thru 1 [H1-xx = 40, 41]
or
KEB Ride-Thru 2 [H1-xx = 42, 43]
.
The drive starts deceleration through KEB operation. When the motor decelerates for the time set in
L2-10
, the
drive measures the DC bus voltage and the status of the digital input set for KEB Ride-Thru. When the DC bus
voltage is less than the level set in
L2-11
, or if the digital input set to KEB Ride-Thru is active, deceleration
continues. When the voltage level is more than the value set to
L2-11
, usual operation continues. The drive
accelerates the motor to the frequency reference value before the power loss, and usual operation continues. When
the KEB Ride-Thru continues to be input after the time set in
L2-02
is expired, the drive uses the KEB Ride-Thru
function to continue to decelerate. When you cancel the KEB Ride-Thru, the motor accelerates again, and usual
operation continues.
Figure 12.124 Use the KEB Ride-Thru to Cancel KEB Operation when Restoration of Power Occurs while the Control
Power (Power Supply to the Control Board) is Maintained
*1
When
L2-07 = 0.00
, the drive accelerates again as specified by the applicable
Acceleration Time [C1-01, C1-
03, C1-05, C1-07]
, and usual operation continues.
KEB Operation when L2-01 = 5 [Kinetic Energy Backup: DecelStop]
The drive starts deceleration through KEB operation. The drive will continue to decelerate until the motor comes
to the minimum output frequency or a complete stop. If you return power during deceleration, the drive continues
to decelerate. If you do not input the Run command, the motor cannot restart.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...