SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
789
Table 12.55 Mechanical Weakening Detection Settings Parameters
Configuration Parameter
Mechanical Deterioration Detection
DO Function Select
•
Terminals 2NO-2CM
•
Terminals 3NO-3CM
•
Terminals 4NO-4CM
H2-01, H2-02, and H2-03 = 66
Operation Selection after Detection
L6-08
Detection Start Time
L6-11
Speed Range
Detection Criteria
L6-08
Detection Level
L6-09
Detection Time
L6-10
Overtorque
Detection Criteria
L6-01
Detection Level
L6-02
Detection Time
L6-03
■
L6-01 Trq Det1 Select
No.
(Hex.)
Name
Description
Default
(Range)
L6-01
(04A1)
Trq Det1 Select
Enables overtorque and undertorque detection and the operation of drives (operation status) after
detection.
0
(0, 1)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-02 [Trq Det1
Level]
for the length of time set in
L6-03 [Trq Det1 Time]
. The drive detects undertorque if the motor current or
output torque is less than the level set in
L6-02
for the length the time set in
L6-03
.
0 : Disabled
1 : Enabled
The behavior is adjusted using parameters
L6-50 [Trq Det1 Type]
,
L6-51 [Trq Det1 Action]
, and
L6-52 [Trq Det1
Condition]
.
■
L6-02 Trq Det1 Level
No.
(Hex.)
Name
Description
Default
(Range)
L6-02
(04A2)
Trq Det1 Level
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
Note:
•
Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
•
You can also use an analog input terminal to supply the torque detection level. To enable this function, set
H3-xx = E [AI Function
Select = OvUntrq Level]
. If you set
L6-02
and
H3-x = E
, the analog input is most important and the drive disables
L6-02
.
■
L6-03 Trq Det1 Time
No.
(Hex.)
Name
Description
Default
(Range)
L6-03
(04A3)
Trq Det1 Time
Sets the detection time for Overtorque/Undertorque Detection 1.
0.1 s
(0.0 - 10.0 s)
■
L6-04 Trq Det2 Select
No.
(Hex.)
Name
Description
Default
(Range)
L6-04
(04A4)
Trq Det2 Select
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0
(0, 1)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-05 [Trq Det2
Level]
for the length of time set in
L6-06 [Trq Det2 Time]
. The drive detects undertorque if the motor current or
output torque is less than the level set in
L6-05
for the length the time set in
L6-06
. Adjust the conditions using
parameters
L6-53, L6-54, and L6-55 [Trq Det2 Type, Trq Det2 Action, and Trq Det2 Condition]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...