660
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Table 12.30 DI-A3 Terminal Function Selection
Terminal
Block
Terminal
Name
BCD, Signed
[F3-01 = 0 to 5]
BCD, Unsigned
[F3-01 = 6]
Binary, Signed
[F3-01 = 7]
8-bit
[F3-03 = 0]
12-bit
[F3-03 = 1]
16-bit
[F3-03 = 2]
8-bit
[F3-03 =
0]
12-bit
[F3-03 = 1]
16-bit
[F3-03 =
2]
TB2
DI0
1 digit (0 -
9)
1
1 digit (0 -
9)
1
1 digit (0 -
9)
1
1 digit (0,
2, 4, 6, 8)
2
bit 0
bit 0
bit 0
DI1
2
2
2
4
bit 1
bit 1
bit 1
DI2
4
4
4
8
bit 2
bit 2
bit 2
DI3
8
8
8
2 digits (0 -
9)
1
bit 3
bit 3
bit 3
DI4
2 digits (0 -
15)
1
2 digits (0 -
9)
1
2 digits (0 -
9)
1
2
bit 4
bit 4
bit 4
DI5
2
2
2
4
bit 5
bit 5
bit 5
DI6
4
4
4
8
bit 6
bit 6
bit 6
DI7
8
8
8
3 digits (0 -
9)
1
bit 7
bit 7
bit 7
TB3
DI8
-
-
3 digits (0 -
15)
1
3 digits (0 -
9)
-
2
-
bit 8
bit 8
DI9
-
2
-
4
-
bit 9
bit 9
DIA
-
4
-
8
-
bit 10
bit 10
DIB
-
8
-
4 digits (0 -
9)
1
-
bit 11
bit 11
DIC
-
-
-
-
4 digits (0 -
15)
-
2
-
-
bit 12
DID
-
-
-
4
-
-
bit 13
DIE
-
-
-
8
-
-
bit 14
DIF
-
-
-
5 digits (0 -
3)
1
-
-
bit 15
TB1
SI
SIGN (encoded) signal
0: Forward run, 1: Reverse run
2
SIGN (encoded) signal
0: Forward run, 1: Reverse run
SE
SET (loaded) signal
1: Loads the value set for DI0 to DIF and SI.
D24V
Internal power supply: 24 V ± 5%
DIC
Input signal common
D0V
Internal power supply common: 0 V
SD
Cable sheath connection terminal (ungrounded)
FE
Cable sheath connection terminal (grounded)
*1
Setting
F3-03 = 2 [D.In Data Length Select = 16-bit]
enables
F3-01 = 6 [D.In Funct Selection = BCD (5-digit), 0.01 Hz]
and a
frequency between 0.00 Hz to 399.8 Hz can be set by the BCD. Note that terminal SI is also used as for data bits. Negative
commands cannot be input as encoding information (positive/negative) cannot be added to the data.
The minimum bit value for the first BCD digit is 2. For this reason, 0.02 Hz is the smallest setting unit available for this frequency
setting. An
oPE05 [Run Cmd/Freq Ref Source Sel Err]
occurs when
F3-03 ≠ 2
while
F3-01 = 6
.
*2
The most significant digit can be set to a value between 0 to 15 when using
“
BCD, Signed
”
. Other digits can be set to a value between
0 to 9.
■
F3-10 D0 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-10
(0BE3)
Expert
D0 Function Selection
Sets the function for terminal D0 of the DI-A3 when
F3-01 = 8 [D.In Funct Selection = MF
Digital Input]
.
0
(0 - 4, 6 - 19F)
■
F3-11 D1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-11
(0BE4)
Expert
D1 Function Selection
Sets the function for terminal D1 of the DI-A3 when
F3-01 = 8 [D.In Funct Selection = MF
Digital Input]
.
0
(0 - 4, 6 - 19F)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...