SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
497
No.
(Hex.)
Name
Description
MFAO Signal Level
Ref.
U4-21
(07DD)
Run Source Selected
Shows the selected Run command source.
The keypad shows the Run command source as
“
XY-nn
”
as specified by these rules:
X:
Ext Ref 1/2 [H1-xx = 9]
selection status
•
1:
b1-02 [Run Comm. Sel 1]
•
2:
b1-16 [Run Comm. Sel 2]
Y: Run command source
•
0: Keypad
•
1: Control circuit terminal
•
3: Modbus communications
•
4: Communication option card
•
7: Q2pack
nn: Run command limit status data
•
00: No limit status.
•
01: The Run command was left ON when the drive stopped in the Programming
Mode.
•
02: The Run command was left ON when switching from LOCAL Mode to
REMOTE Mode.
•
03: The Run command is in standby after the drive was energized until the soft
charge bypass contactor turns ON.
Note:
The drive will detect
Uv1 [DC Bus Undervoltage]
or
Uv [Undervoltage]
if the soft
charge bypass contactor does not turn ON after 10 s.
•
04: Restart after run stop is prohibited.
•
05: Fast stop has been executed using the MFDI terminal. Or, the motor has ramped
to stop by pressing the STOP key on the keypad.
•
06:
b1-17 = 1 [RUN@PowerUp Selection = Disregard RUN]
is set.
•
07: During baseblock while coast to stop with timer.
•
08: Frequency reference is below
E1-09 [Min Output Frequency]
during baseblock.
•
09: Waiting for the Enter command from PLC.
No signal output The
keypad shows the Run
command source as
"XY-nn" as specified by
these rules: available
-
U4-22
(07DE)
Mbus CmdWord Value
Shows the operation signal (register 0001H) sent to the drive from Modbus
communications as a 4-digit hexadecimal number (zero suppress). The keypad shows
the operation signal as specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Multi-function input 8
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
No signal output
available
-
U4-23
(07DF)
Option CmdWord Value
Shows the operation signal (register 0001H) sent to the drive from Modbus
communications as a 4-digit hexadecimal number. The keypad shows the operation
signal as specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Multi-function input 8
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
No signal output
available
-
U4-24
(07E6)
No of Travels(L)
Shows the lower 4 digits of the drive run count.
Note:
The drive run count appears as an 8-digit number. The upper 4 digits of
U4-25 [No
of Travels(H)]
and the lower 4 digits of
U4-24
appears.
No signal output
available
-
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...