244
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Table 6.10 Modbus Communications Command Data
Regis
ter No.
(Hex.)
Description
0000
Reserved
0001
Run command, multi-function input command
bit 0
When
H5-12 = 0
, Forward run/stop
1: Forward run, 0: Stop
When
H5-12 = 1
, run/stop
1: Run, 0: Stop
bit 1
When
H5-12 = 0
, Reverse run/stop
1: Reverse run, 0: Stop
When
H5-12 = 1
, Forward/Reverse run
1: Reverse, 0: Forward run
bit 2
External Fault
1: EF0 [Option Card External Fault]
bit 3
Fault Reset
1: Reset command
bit 4
Multi-function input 1
When
H1-01 = 1 [Forward Run]
, the multi-function input
command is
“
ComRef.
”
Note:
When you switch the bit ON as ComRef, the frequency
reference source changes to Modbus communications.
When you connect a communication option to the drive,
the frequency reference source gives priority to the
communications option.
bit 5
Multi-function input 2
When the multi-function input command is
H1-02 = 2
[Reverse Run]
, bit 5 is
“
ComCtrl.
”
Note:
When you switch the bit ON as ComCtrl, the Run
Command source changes to Modbus communications.
When you connect a communication option to the drive,
the Run Command source gives priority to the
communications option.
bit 6
Multi-function input 3
bit 7
Multi-function input 4
bit 8
Multi-function input 5
bit 9
Multi-function input 6
bit A
Multi-function input 7
bit B
Multi-function input 8
bit C - F
Reserved
0002
Frequency
Reference
o1-03 [FrqDisplay Unit Selection]
(unsigned) sets the units.
0003
Output
voltage gain
Units: 0.1 %
Setting range: 20 (2.0%) to 2000 (200.0%), the default value
at energize: 1000 (100.0%)
0004
Torque reference/torque limit (0.1% signed)
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Setting for the multi-function analog monitor output terminal 1 (10 V/4000
H)
0008
Setting for the multi-function analog monitor output terminal 2 (10 V/4000
H)
Regis
ter No.
(Hex.)
Description
0009
MFDO setting
bit 0
MFDO (terminal 2NO-2CM)
1: ON, 0: OFF
bit 1
MFDO (terminal 3NO-3CM)
1: ON, 0: OFF
bit 2
MFDO (terminal 4NO-4CM)
1: ON, 0: OFF
bit 3 - 5
Reserved
bit 6
1: bit 7 function is enabled
bit 7
Fault relay output (terminal 1NO/1NC-1CM)
1: ON, 0: OFF
bit 8 - F
Reserved
000A
Pulse train output (Units: 1/1 Hz, setting range: 0 to 32000)
000B -
000E
Reserved
000F
Command selection setting
bit 0
Reserved
bit 1
Input for the PID setpoint
1: Enables target values from Modbus
bit 2
Torque reference/torque limit input
1: Enables setting values from Modbus
bit 3
Torque Compensation Input
1: Enables setting values from Modbus
bit 4
Reserved
bit 5
PID feedback from the Modbus
1: Enables PID feedback (15FF (Hex.)) from Modbus
bit 6 - B
Reserved
bit C
Terminal DI5 input of broadcast message
1: Enabled, 0: Disabled
bit D
Terminal DI6 input of broadcast message
1: Enabled, 0: Disabled
bit E
Terminal DI7 input of broadcast message
1: Enabled, 0: Disabled
bit F
Terminal DI8 input of broadcast message
1: Enabled, 0: Disabled
0010 -
001A
Reserved
001B
Analog monitor option AO-A3 analog output 1 value (10 V/4000 (Hex.))
001C
Analog monitor option AO-A3 analog output 2 value (10 V/4000 (Hex.))
001D
Digital output option DO-A3 output value (binary)
001E -
001F
Reserved
15C0
bit 0
Extended multi-function input command 1
bit 1
Extended multi-function input command 2
bit 2
Extended multi-function input command 3
bit 3 - F
Reserved
3004
Time Setting
Setting range: 0000 to 2359 (decimal), the default value at energize: 0000
Set the hour and the minute in HHMM format.
•
HH: 00 to 23 (decimal)
•
MM: 00 to 59 (decimal)
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...