SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
605
Item
Heavy Duty Rating 1 (HD1)
Heavy Duty Rating 2 (HD2)
Normal Duty Rating 1 (ND1)
Normal Duty Rating 2 (ND2)
Load
Characteristics
Application
A high overload tolerance is necessary during start up, acceleration,
deceleration, and equivalent conditions.
•
Extruder
•
Conveyor
•
Cranes and hoists
•
Constant torque or high overload capacity are necessary.
Overload tolerance is not necessary.
•
Fan
•
Pump
•
Blower
Overload
Tolerance
150% - 60 seconds
110% - 60 seconds
Stall Prevent
Level during
Accel
150%
110%
Stall Prevent
Level during Run
150%
110%
Carrier Frequency
2 kHz
2 kHz Swing-PWM
Note:
•
Set the stall prevention level during acceleration with
L3-02
and the stall prevention level during run with
L3-06
.
•
Changing
C6-01
also changes the maximum capacity of applicable drive motors. The drive automatically changes the setting values
E2-xx
and
E4-xx
to applicable values. The drive also automatically changes these parameters that depend on motor output:
–
b8-04 [eSave Coef. Value]
–
C5-17 [Motor Inertia]
–
C5-37 [M2 Inertia]
–
L2-03 [Min Baseblck Time]
–
L3-24 [Acc@Rated Torque]
–
n5-02 [Mot Inertia Acceleration Time]
■
C6-02 Carrier Frequency Selection
No.
(Hex.)
Name
Description
Default
(Range)
C6-02
(0224)
Carrier Frequency Selection
Sets the carrier frequency for the transistors in the drive.
Determined by A1-02, C6-
01, and o2-04
(Determined by A1-02)
Changes to the switching frequency will decrease audible noise and decrease leakage current.
Note:
Increasing the carrier frequency to more than the default setting will automatically decrease the drive current rating.
1 : 2.0 kHz
2 : 5.0 kHz (4.0 kHz for AOLV/PM)
3 : 8.0 kHz (6.0 kHz for AOLV/PM)
4 : 10.0 kHz (8.0 kHz for AOLV/PM)
5 : 12.5 kHz (10.0 kHz for AOLV/PM)
6 : 15.0 kHz (12.0 kHz AOLV/PM)
7 : Swing PWM 1 (Audible Sound 1)
8 : Swing PWM 2 (Audible Sound 2)
9 : Swing PWM 3 (Audible Sound 3)
A : Swing PWM 4 (Audible Sound 4)
F : User (C6-03 to C6-05)
Use
C6-03 to C6-05
to set detailed setting values.
Note:
The carrier frequency for Swing PWM 1 is equivalent to 2.0 kHz. Swing PWM applies a special PWM pattern to decrease the audible
noise.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...