SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
■
L6-57 MechF AbsSpeed
No.
(Hex.)
Name
Description
Default
(Range)
L6-57
(04D3)
MechF AbsSpeed
Sets the speed where the drive detects mechanical deterioration and how the drive operates
(operation status) after detection. Only available when
L6-08 = 1 [MechF Enable = Enabled]
.
0
(0, 1)
■
L6-58 MechF Method
No.
(Hex.)
Name
Description
Default
(Range)
L6-58
(04D4)
MechF Method
Sets the speed where the drive detects mechanical deterioration and how the drive operates
(operation status) after detection. Only available when
L6-08 = 1 [MechF Enable = Enabled]
.
Use parameter L6-57 [MechF AbsSpeed] to either use absolute speed or signed speed value.
0
(0, 1)
◆
L7: TORQUE LIMIT
The torque limit function limits the internal torque reference for the drive to limit the quantity of torque generated
by the motor to a constant quantity This function keeps the torque applied to loads and regenerative torque less
than a set quantity. This function also prevents damage to machinery and increases the reliability of continuous
operation. You can set torque limits individually for the four quadrants, which include torque direction (motoring/
regeneration) and direction of motor rotation (forward/reverse). When the torque reference value is at the set
torque limit, the MFDO terminal set for During Torque Limit
[H2-xx = 30]
activates.
Note:
•
The drive output current limits maximum output torque. The drive limits torque to 150% of the rated output current for Heavy Duty
Rating (HD) and to 120% of the rated output current for Normal Duty Rating (ND). The actual output torque is not more than the limits
of the drive rated output current when you set the torque limit to a high value.
•
When you use torque limits for lifting applications, do not lower the torque limit value too much. When the torque limit function is
triggered, falls and rollbacks can occur because of sudden acceleration stops and stalls of the motor.
■
Configuring Settings
Use one of these methods to set torque limits:
•
Use
L7-01
to
L7-04 [FW Torque Limit to RV Reg. TrqLimit]
to individually set the four torque limit quadrants.
•
Use MFAI to individually set the four torque limit quadrants. Set
H3-02, H3-06, H3-10 = 9, B, C [AI Function
Select = FW Trq Lim, Rev Trq Lim, RegenTrqLim]
.
•
Use MFAI to set all four torque limit quadrants together. Set
H3-02, H3-06, H3-10 = D [GenerTrqLim]
.
•
Use a communication option to set all four torque limit quadrants together.
shows the configuration method for each quadrant.
Figure 12.138 Torque Limits and Analog Input Setting Parameters
Note:
When
L7-01 to L7-04
and analog inputs or communication option torque limits set torque limits for the same quadrant, the lower value
is enabled.
In this example of parameter settings, the torque limit for quadrant 1 is 130% and the torque limit for quadrants 2, 3, and 4 is 150%.
Settings:
L7-01
= 130%,
L7-02, L7-03, L7-04
= 200%, MFAI torque limit = 150%
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...