608
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
12.4
d: REFERENCE
d parameters
set the frequency reference input method and dead band range. They also set torque control, field
weakening, and field forcing functions.
WARNING!
Sudden Movement Hazard. Always check the operation of any fast stop circuits after they are wired. Fast stop
circuits are required to provide safe and quick shutdown of the drive. Prepare to initiate an emergency stop during the test run.
Operating a drive with untested emergency circuits could result in death or serious injury.
WARNING!
Crush Hazard. Do not use this drive in lifting applications without installing external safety circuitry to prevent
accidental dropping of the load. The drive does not possess built-in load drop protection for lifting applications. Install electrical
and/or mechanical safety circuit mechanisms independent of drive circuitry. Failure to comply could result in death or serious
injury from falling loads.
◆
d1: FREQUENCY REFERENCE
shows the frequency reference input method, command source selection method and priority
descriptions.
Figure 12.53 Frequency Reference Setting Hierarchy
■
Multi-Step Speed Operation
The drive has a multi-step speed operation function that can set many frequency references in advance. Set
frequency references in
d1-xx
parameters. You can select the set frequency references with MFDI signals from an
external source. Activate and deactivate the digital input to select the frequency reference to change the motor
speed in steps. You can use the 16-step frequency reference and one Jog Frequency Reference (JOG command) to
switch the speed to the maximum 17-step speeds.
Note:
•
The Jog Frequency Reference (JOG command) overrides all other frequency references.
•
You can use the MFDI to switch the frequency reference when the motor is running. The drive will apply the enabled acceleration and
deceleration times.
•
The default settings for Multi-Step Speed Reference 1 (master frequency reference) and Multi-Step Speed Reference 2 (auxiliary
frequency reference) are the analog frequency reference.
Also, voltage command input terminal A1 and current input terminal A2 for Multi-Step Speed Reference 1 (master frequency
reference) are added internally by default. The drive uses Multi-Step Speed Reference 1 when the signal is connected to an analog
input terminal.
■
Setting Procedures for Multi-step Speed Operation
Use an Analog Input as Reference 1 and 2
This section gives information about the procedures to set these examples:
•
Multi-Step Speed 6 (6 types of frequency references)
•
When you set the voltage input of analog inputs from terminals AI1 and AI3 to -10 V to +10 V
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...