When the MFDI terminal set to
PID Disable [H1-xx = 6A]
activates, the drive disables fault detection.
4 : AL+DO@PID Enable
The drive detects
FbL
and
FbH
. The MFDO terminal set for
PID Feedback Low
or
PID Feedback High
activates.
The output terminal set for
Alarm [H2-01 to H2-03 = 4]
activates and the drive continues operation.
When the MFDI terminal set to
PID Disable [H1-xx = 6A]
activates, the drive disables fault detection.
5 : FLT+DO@PID Enable
The drive detects
FbL
and
FbH
. The output terminal set for
Fault [H2-01 to H2-03 = 3]
activates and the motor
coasts to stop.
When the MFDI terminal set to
PID Disable [H1-xx = 6A]
activates, the drive disables fault detection.
■
b5-13 Fdback Loss Lvl
No.
(Hex.)
Name
Description
Default
(Range)
b5-13
(01B1)
Fdback Loss Lvl
Sets the level that triggers
PID Feedback Loss [FbL]
as a percentage of
E1-04 [Max Output
Frequency]
.
0%
(0 - 100%)
The drive detects
PID Feedback Loss [FbL]
when the feedback signal decreases to less than the level set in
b5-13
for longer than the time set in
b5-14 [Fdback Loss Time]
.
■
b5-14 Fdback Loss Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-14
(01B2)
Fdback Loss Time
Sets the length of time that PID Feedback must be less than
b5-13 [Fdback Loss Lvl]
to detect
PID Feedback Loss [FbL]
.
1.0 s
(0.0 - 25.5 s)
■
b5-15 Sleep Start Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-15
(01B3)
Sleep Start Level
Sets the output level that triggers the PID Sleep function.
Determined by A1-02
(0.0 - 590.0)
The drive goes into Sleep mode when the PID output or frequency reference is less than
b5-15
for longer than the
time set to
b5-16 [Sleep Delay Time]
. The drive continues operation when the PID output or frequency reference
is more than
b5-15
for longer than the time set to
b5-16
.
■
b5-16 Sleep Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-16
(01B4)
Sleep Delay Time
Sets a delay time to start or stop the PID Sleep function.
0.0 s
(0.0 - 25.5 s)
■
b5-17 PID Accel/Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-17
(01B5)
PID Accel/Decel Time
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive.
This is a soft-starter for the PID setpoint.
0.5 s
(0.0 - 6000.0 s)
The drive usually uses the acceleration and deceleration times set in
C1: ACCEL / DECEL
, but when PID control
is enabled, the drive applies
C1-xx
after PID output. If you frequently change the PID setpoint, the drive
responsiveness decreases. When resonance with PID control causes hunting, overshoot, or undershoot, set
b5-17
for longer acceleration and deceleration times.
Decrease
C1-xx
until hunting stops, then use
b5-17
to check the acceleration and deceleration. To enable and
disable the setting in
b5-17
through an MFDI terminal, set
PID SS Cancel [H1-xx = 75]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...