SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
833
You can use
to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL
Mode is selected,
on the keypad will come on.
WARNING!
Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when setting b1-07 = 2
[LO/RE Run Selection = Accept RUN]. Clear all personnel from rotating machinery and electrical connections prior to switching
control sources. Failure to comply may cause death or serious injury.
WARNING!
Sudden Movement Hazard. Fully examine all mechanical and electrical connections before you change o2-01 [LO/
RE Key Selection of Function] or b1-07 [LO/RE Run Selection]. If b1-07 = 2 [Accept RUN] and there is an active Run command
when you switch from LOCAL to REMOTE Mode, the drive can start suddenly. Failure to obey can cause serious injury or
death.
Table 12.57 Function Settings via o2-01 through b1-07
Function Selection
LOCAL/REMOTE Run Selection
Switching from LOCAL Mode to
REMOTE Mode
Switching from REMOTE Mode to
LOCAL Mode
o2-01 = 0 [Disabled]
b1-07 = 1 [Cycle RUN]
The drive will not switch modes.
The drive will not switch modes.
b1-07 = 2 [Accept RUN]
o2-01 = 1 [Enabled]
b1-07 = 1 [Cycle RUN]
The drive will not start operating although
the Run command is active. When you set
Run command to active again, the drive
will start to run.
The drive cannot operate because the Run
command is not enabled.
b1-07 = 2 [Accept RUN]
When the Run command is active, the
drive will start to run immediately when
the mode switches from LOCAL to
REMOTE.
The drive cannot operate because the Run
command is not enabled.
■
o2-02 STOP Key Selection of Function
No.
(Hex.)
Name
Description
Default
(Range)
o2-02
(0506)
STOP Key Selection of
Function
Sets the function to stop the drive with the
button on the keypad when the Run command
source for the drive is REMOTE (external) and not assigned to the keypad.
1
(0, 1)
0 : Disabled
1 : Enabled
stays enabled when the Run command source has not been assigned to the keypad.
To start the drive again after you push
to stop operation, turn the external Run command OFF and ON
again.
■
o2-03 UserPar Set Default Values
No.
(Hex.)
Name
Description
Default
(Range)
o2-03
(0507)
UserPar Set Default Values
Sets the function to keep the settings of changed parameters as user parameter defaults to use
during initialization.
0
(0 - 2)
When you set this parameter to 1, the drive saves changed parameter settings as user parameter setting values in a
part of the memory that is isolated from drive parameters.
When you set
A1-03 = 1110 [Init Parameters = User Initialization]
to initialize the drive, the drive resets the
internal parameter setting values to those user parameter setting values.
0 : No change
1 : Set defaults
Saves changed parameter settings as user-set default for User Initialization.
Set
o2-03 = 1 [Set defaults]
, then push
on the keypad to save the user parameter setting values. After the drive
saves the setting value,
o2-03
automatically resets to
0
.
2 : Clear all
Deletes all of the saved user parameter setting values.
To delete the user parameter setting values, set this parameter to 2 and push
on the keypad. The drive will
automatically reset
o2-03
to
0
. If you delete the user parameter setting values, you cannot set
A1-03 = 1110
to
initialize parameters.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...