78
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
WARNING!
Electrical Shock Hazard. Do not connect the AC power line to the output terminals of the drive. Failure to obey can
cause death or serious injury by fire.
NOTICE:
Make sure that you align the phase order for the drive and motor when you connect the motor to drive output
terminals U/T1, V/T2, and W/T3. Failure to obey correct wiring procedures can cause the motor to run in reverse if the phase
order is incorrect.
NOTICE:
Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to obey can cause
damage to the drive, phase-advancing capacitors, LC/RC noise filters, and leakage breakers (ELCB, GFCI, or RCM/RCD).
■
Cable Length Between Drive and Motor
When the wiring between the drive and the motor is too long, voltage drop along the motor cable can decrease
motor torque, usually at low frequency output. If you connect motors in parallel with long motor cable, this is also
a problem. Drive output current increases when the leakage current from the cable increases. An increase in
leakage current can cause overcurrent and decrease the precision of the current detection.
Use the values in
to adjust the drive carrier frequency. When the system configuration makes the motor
wiring distance more than 100 m (328 ft), do not use metal conduits or use isolated cables for each phase to
decrease stray capacitance.
Table 3.2 Carrier Frequency against Cable Length Between Drive and Motor
Cable Length Between Drive and
Motor
Up to 50 m (164 ft.)
Up to 100 m (328 ft.)
More than 100 m (328 ft.)
Carrier Frequency
15 kHz or less
5 kHz or less
2 kHz or less
Note:
•
To set the carrier frequency in a drive that is operating more than one motor, calculate the cable length as the total distance of wiring to
all connected motors.
•
In
A1-02 = 5 or 6 [Control Method = PM OLVector or PM AOLVector]
, the maximum cable length is 100 m (328 ft.).
•
When you connect to a PM motor, it can be necessary to adjust the overcurrent detection. Refer to
L8-27 OverCurr Det Gain on page
for more information.
■
Ground Wiring
Follow the precautions to wire the ground for one drive or a series of drives.
WARNING!
Electrical Shock Hazard. Make sure that the protective ground wire complies with technical standards and local
safety regulations. The leakage current of the drive will be more than 3.5 mA. The IEC/EN 61800-5-1:2007 standard specifies
that you must wire the power supply to automatically turn off when the protective ground wire disconnects. You can also
connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire) or 16 mm
2
(aluminum wire).
Failure to obey these standards can cause death or serious injury.
WARNING!
Electrical Shock Hazard. Ground the neutral point on the power supply to comply with the EMC Directive before
turning on the EMC filter or if there is high resistance grounding. If the EMC filter is switched ON without the neutral point being
grounded or if there is high resistance grounding, it can cause death or serious injury.
WARNING!
Electrical Shock Hazard. Use a ground wire that complies with technical standards on electrical equipment and use
the minimum length of ground wire. Incorrect equipment grounding can cause serious injury or death from dangerous electrical
potentials on the equipment chassis.
WARNING!
Electrical Shock Hazard.
Correctly ground the ground terminals. Obey federal and local electrical wiring codes for correct grounding methods.
• 200 V class: ground to 100
Ω
or less
• 400 V class: ground to 10
Ω
or less
Failure to obey can cause death or serious injury from contacting ungrounded electrical equipment.
NOTICE:
Do not share the ground wire with other devices, for example welding machines or large-current electrical equipment.
Incorrect equipment grounding can cause drive or equipment malfunction from electrical interference.
NOTICE:
To use more than one drive, obey the instructions to ground all drives. Incorrect equipment grounding can cause
incorrect operation of drives and equipment.
Do not loop the grounding wire when connecting more than one drive.
Figure 3.14 Wiring More than One Drive
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...