278
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Code
Name
Causes
Possible Solutions
oL2
Drive Overload
The load is too heavy.
Decrease the load.
The acceleration/deceleration times or cycle times
are too short.
•
Examine the acceleration/deceleration times and the motor
start/stop frequencies (cycle times).
•
Increase the value set in Acceleration/Deceleration Times
C1-
01 to C1-08
.
The V/f pattern does not fit the motor qualities.
•
Examine the ratios between the V/f pattern frequency and
voltage. Lower the voltage if it is too high compared to the
frequency.
•
Adjust V/f Pattern Parameters
E1-04 to E1-10
. Lower the
values set in
E1-08 [Mid A Voltage]
and
E1-10 [Min Output
Voltage]
For motor 2, adjust
E3-04 to E3-10
.
Note:
If
E1-08
and
E1-10
are set too low, the overload tolerance is
will decrease at low speeds.
The drive capacity is too small.
Replace the drive with a larger capacity model.
Overload occurred while running at low speed.
•
Decrease the load when running at low speed.
•
Replace the drive with a larger capacity model.
•
Decrease the value set in
C6-02 [Carrier Frequency
Selection]
.
The torque compensation gain is too large.
Decrease the value set in
C4-01 [Trq Comp Gain]
to make sure
that the motor does not stall.
The speed search-related parameters are set
incorrectly.
•
Examine the settings for all speed search related parameters.
•
Adjust
b3-03 [SpSrch Deceleration Time]
.
•
Set
b3-24 = 1 [SpSrch Method Selection = Speed Estimation]
after Auto-Tuning.
Phase loss in the input power supply is causing the
output current to change.
•
Correct any wiring errors in the main circuit drive input power.
•
Make sure that there is no phase loss, and repair problems.
Note:
•
The drive detects this fault if the electronic thermal protector of the drive started the motor overload protection.
•
Do a Fault Reset to clear the fault.
•
L5-07 [OL1-4 Auto-Reset Select]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
oL3
Overtorque Detection 1
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load.
Adjust
L6-02 [Trq Det1 Level]
and
L6-03 [Trq Det1 Time]
settings.
Note:
•
The drive detects this fault if the drive output current is more than the level set in
L6-02
for longer than
L6-03
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in
L6-01 [Trq Det1 Select]
.
•
L5-07 [OL1-4 Auto-Reset Select]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
oL4
Overtorque Detection 2
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load.
Adjust
L6-05 [Trq Det2 Level]
and
L6-06 [Trq Det2 Time]
settings.
Note:
•
The drive detects this fault if the drive output current is more than the level set in
L6-05
for longer than
L6-06
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in
L6-04 [Trq Det2 Select]
.
•
L5-07 [OL1-4 Auto-Reset Select]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
oL5
Mechanical Weakening Detection 1
The drive detected overtorque as specified by the
conditions for mechanical weakening detection set
in
L6-08 [MechF Enable]
, and in
L6-56, L6-57, L6-
58 [MechF Action, MechF AbsSpeed, MechF
Method]
.
Do a deterioration diagnostic test on the machine side.
Note:
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in
L6-08
, and in
L6-56, L6-57, L6-58 [MechF Action, MechF AbsSpeed, MechF
Method]
.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...