494
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
No.
(Hex.)
Name
Description
MFAO Signal Level
Ref.
U2-13
(008C)
DrvStat@PrevFault
Shows the operation status of the drive at the most recent fault where 1 = (ON) and 0 =
(OFF).
For example,
U2-13
shows
“
00000001
”
during run.
Use
U1-12 [Drive Status]
to monitor the actual drive status.
bit 0 : During run
bit 1 : During zero-speed
bit 2 : During reverse
bit 3 : During fault reset signal input
bit 4 : During speed agreement
bit 5 : Drive ready
bit 6 : During minor fault detection
bit 7 : During fault detection
No signal output
available
-
U2-14
(008D)
OpeTime@PreFault
Shows the cumulative operation time of the drive at the fault that occurred most
recently.
Use
U4-01 [Cumulative OpeTime]
to monitor the actual cumulative operation time.
Unit: 1 h
No signal output
available
-
U2-15
(07E0)
SFSFreq@PrevFault
Shows the output frequency after soft start at the fault that occurred most recently.
Use
U1-16 [SFS Output Frequency]
to monitor the actual output frequency after soft
start.
Unit: 0.01 Hz
No signal output
available
-
U2-16
(07E1)
qCurrent@PrevFault
Shows the q-axis current of the motor at the fault that occurred most recently.
Use
U6-01 [Iq Sec Current]
to monitor the actual q-Axis current of the motor.
Unit: 0.1 %
No signal output
available
-
U2-17
(07E2)
dCurrent@PreFault
Shows the d-axis current of the motor at the fault that occurred most recently.
Use
U6-02 [Id ExcCurrent]
to monitor the actual d-Axis current of the motor.
Unit: 0.1 %
No signal output
available
-
U2-19
(07EC)
RotorDev@PrevFault
Shows the amount of control axis deviation (Δθ) at the fault that occurred most recently.
Use
U6-10 [ContAxisDeviation]
to monitor the actual amount of control axis deviation
(Δθ).
Unit: 0.1 °
No signal output
available
-
U2-20
(008E)
DrvTemp@PreFault
Shows the heatsink temperature at the fault that occurred most recently.
Use
U4-08 [Heatsink Temperature]
to monitor the actual temperature of the heatsink.
Unit: 1 °C
No signal output
available
-
U2-21
(1166)
Expert
STPoSt@PrevFault
Monitors conditions to detect
STPo [Motor Step-Out Detected]
faults. The bit for each
condition is displayed as ON or OFF.
bit 0 : Excessive current
bit 1 : Induced voltage deviation
bit 2 : d-axis current deviation
bit 3 : Motor lock at startup
bit 4 : Acceleration stall continue
bit 5 : Acceleration stall repeat
bit 6 : Not used (normal value of 0).
bit 7 : Not used (normal value of 0).
No signal output
available
-
◆
U3: FAULT HISTORY
No.
(Hex.)
Name
Description
MFAO Signal Level
Ref.
U3-01 to U3-10
(0090 - 0093)
(0804 - 0809)
1st to 10th Newest Fault
Shows the fault history of the first to tenth most recent faults.
Note:
The drive saves the
U3-01 to U3-04 [1st to 4th Newest Fault]
fault histories to two
types of registers at the same time for the Modbus communications.
No signal output
available
-
U3-11 to U3-20
(0094 - 0097,
080E - 0813)
1st to 10th NewstFlt
Timing
Shows the cumulative operation time when the first to tenth most recent faults occurred.
Unit: 1 h
Note:
The drive saves the
U3-11 to U3-14 [1st to 4th NewstFlt Timing]
the cumulative
operation time to two types of registers at the same time for the Modbus
communications.
No signal output
available
-
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...