SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
495
◆
U4: MAINTENANCE
No.
(Hex.)
Name
Description
MFAO Signal Level
Ref.
U4-01
(004C)
Cumulative OpeTime
Shows the cumulative operation time of the drive.
Use parameter
o4-01 [Cum.Oper TimeSetting]
to reset this monitor. Use parameter
o4-
02 [Cum.Oper TimeSelect]
to select the cumulative operation times from:
•
The time from when the drive is energized until it is de-energized.
•
The time at which the Run command is turned ON.
The maximum value that the monitor will show is
99999
. The value then resets and
starts counting again from
0
.
Unit: 1 h
Note:
The Modbus communication data is shown in 10 h units. Use register 0099H for
data in 1 h units.
No signal output
available
-
U4-02
(0075)
Num of Run Commands
Shows how many times that the drive has received a Run command.
Use parameter
o4-13 [NumOfRunCom Init Counter]
to reset this monitor. The
maximum value that the monitor will show is
65535
. The value then resets and starts
counting again from
0
.
Unit: 1
No signal output
available
-
U4-03
(0067)
Fan Oper.Time
Shows the cumulative operation time of the cooling fans.
Use parameter
o4-03 [Fan.Oper Setting]
to reset this monitor. The maximum value that
the monitor will show is
99999
. The value then resets and starts counting again from 0.
Unit: 1 h
Note:
The Modbus communication data is shown in 10 h units. Use register 009BH for
data in 1 h units.
No signal output
available
-
U4-04
(007E)
Cool Fan Maintenance
Shows the cumulative operation time of the cooling fans as a percentage of the
replacement life of the cooling fans.
Use parameter
o4-03 [Fan.Oper Setting]
to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
No signal output
available
-
U4-05
(007C)
Capacitor Maintenance
Shows the operation time of the electrolytic capacitors for the main circuit and control
circuit as a percentage of the replacement life of the electrolytic capacitors.
Use parameter
o4-05 [Cap.Maint.Setting]
to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is 90%.
No signal output
available
-
U4-06
(07D6)
SoftChgRelay Maint
Shows the operation time of the soft charge bypass relay as a percentage of the
replacement life of the soft charge bypass relay.
Use parameter
o4-07 [PreChgRly Preset Maintenance Cnt]
to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
No signal output
available
-
U4-07
(07D7)
IGBT Maintenance
Shows the operation time of the IGBTs as a percentage of the replacement life of the
IGBTs.
Set parameter
o4-09 [IGBT Preset Maintenance Cnt]
to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
No signal output
available
-
U4-08
(0068)
Heatsink Temperature
Shows the heatsink temperature of the drive.
Unit: 1 °C
10 V: 100 °C
-
U4-09
(005E)
LED Check
Turns on all of the keypad LEDs to make sure that the LEDs operate correctly.
Push
with
U4-09
shown on the keypad.
All LEDs on the keypad will turn on.
Note:
When Safety input 2 CH is open (STo), READY will flash.
No signal output
available
-
U4-10
(005C)
kWh Lower 4Digits
Displays the lower 4 digits of the watt hour value for the drive.
Unit: 1 kWh
Note:
The watt hour is displayed in 9 digits. Parameter
U4-11 [kWh Upper 5Digits]
displays the upper 5 digits and
U4-10
displays the lower 4 digits.
Example for 12345678.9 kWh:
U4-10
: 678.9 kWh
U4-11
: 12345 MWh
No signal output
available
-
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...