SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
815
•
J
Motor
= Moment of inertia of motor (kg m
2
)
•
n
rated
= Motor rated speed (min
-1
, r/min)
•
T
rated
= Motor rated torque (N m)
You can also use this formula to find the motor acceleration time:
•
f
rated
= Motor rated frequency (Hz)
•
P = Number of motor poles
Calculate the Motor Acceleration Time
Use this procedure to calculate the motor acceleration time:
1. Use
A1-02 [Control Method]
to set the control method.
2. Disconnect the motor and load.
3. Run Auto-Tuning to set motor parameters.
When you cannot do Auto-Tuning, manually set motor parameters with the information on the motor
nameplate or test reports. Set the
E2 parameters
for induction motors. Set the
E5 parameters
for PM motors.
4. Set
C5 parameters [C5: ASR - SPEED REGULATION]
.
5. Set
C1-01 [Accel Time 1] = 0.
6. Set
L7-01 [FW Torque Limit]
to 100%.
7. Set the frequency reference to the same value as the motor rated speed.
8. Measure the length of time for the motor to reach the rated speed.
Show
U1-05 [Motor Speed]
on the keypad and enter the Run command (forward run).
9. Stop the motor.
10. Set
n5-02
to the measured motor acceleration time value.
Reset all of the parameters that you changed to the previous setting values.
■
n5-03 FF Control Gain
No.
(Hex.)
Name
Description
Default
(Range)
n5-03
(05B2)
FF Control Gain
Sets the ratio between load inertia and motor inertia. Inertia Tuning automatically sets the
Feedforward Control Gain value.
1.00
(0.00 - 100.00)
When you cannot do Inertia Tuning, use this procedure to set
n5-03
:
1. Set
n5-02 [Mot Inertia Acceleration Time]
.
2. Connect the motor and load.
3. Set
C1-01 [Accel Time 1] = 0
.
4. Use
L7-01 to L7-04 [FW Torque Limit to RV Reg. TrqLimit]
to set the expected test run torque limit levels.
5. Set the frequency reference as specified by the high speed range of the machine.
6. Measure the length of time for the motor to reach the command reference speed.
Show
U1-05 [Motor Speed]
on the keypad and enter the Run command.
7. Stop the motor.
8. Replace the values in the this formula and set
n5-03
to the value of the formula.
•
t
accel
= Acceleration time (s)
•
f
rated
= Motor rated frequency (Hz)
•
T
Lim_Test
= Test run torque limit (%)
•
f
ref_Test
= Test run frequency reference (Hz)
WARNING!
Sudden Movement Hazard. Machinery can accelerate suddenly. Do not use this function with machinery that must
not accelerate suddenly. Failure to obey can cause death or serious injury.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...