SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Note:
When
b2-01 ≤ E1-09 [Min Output Frequency]
, the drive will start Short Circuit Braking from the frequency set in
E1-09
. If
b2-01 and
E1-09 = 0 Hz
, the drive will not do Short Circuit Braking.
•
A1-02 = 3 or 7 [CLVector or PM CLVector]
or
A1-02 = 4 [Adv OLVector]
and
n4-72 = 2 [With PG]
In these control methods,
b2-01
sets the starting frequency for Zero Speed Control at Stop. When the output
frequency is less than or equal to the value set in
b2-01
, the drive will do Zero Speed Control for the time set in
b2-04
.
Figure 12.20 Zero Speed Control at Stop
Note:
When
b2-01 ≤ E1-09 [Min Output Frequency]
, the drive will start Short Circuit Braking from the frequency set in
E1-09
.
■
b2-02 DCI Braking Current
No.
(Hex.)
Name
Description
Default
(Range)
b2-02
(018A)
DCI Braking Current
Sets the DC Injection Braking current as a percentage of the drive rated current.
50%
(0 - 100%)
When the DC Injection Braking current is more than 50%, the drive decreases the carrier frequency to 1 kHz. The
motor rated current determines how much DC Injection Braking current that the drive can use.
The DC Injection Braking current level has an effect on the strength of the magnetic field that locks the motor
shaft. As the current level increases, the motor windings will supply more heat. Do not set this parameter higher
than the level that is necessary to hold the motor shaft.
Note:
When
A1-02 = 4 [Control Method = Adv OLVector]
and
n4-72 = 2 [Spd Fbk Mode = With PG]
, the drive ignores the
b2-02
setting and
does initial excitation.
■
b2-03 DCInj Time@Start
No.
(Hex.)
Name
Description
Default
(Range)
b2-03
(018B)
DCInj Time@Start
Sets the DC Injection Braking Time at stop. Sets the zero speed control at stop in CLV, AOLV, or
CLV/PM.
A1-02 = 4: 0.03 s
Other than A1-02 = 4: 0.00
s
(0.00 - 10.00 s)
This function stops then restarts a coasting motor and increases motor flux to make high starting torque (a process
called initial excitation). Set this parameter to 0.00 to disable the function.
Note:
To restart a coasting motor, use DC Injection Braking to stop and then restart the motor, or enable Speed Search. DC Injection Braking
can trigger
ov [Overvoltage]
or
oC [Overcurrent]
.
■
b2-04 DCInj Time@Stop
No.
(Hex.)
Name
Description
Default
(Range)
b2-04
(018C)
DCInj Time@Stop
Sets the DC Injection Braking Time at stop. Sets the zero speed control at stop in CLV, AOLV, or
CLV/PM.
Determined by A1-02
(0.00 - 10.00 s)
This function fully stops a motor with a large inertia during deceleration and will not let the inertia continue to
rotate the motor.
Set this parameter to 0.00 to disable the function.
When a longer time is required to stop the motor, increase the value.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...