SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
629
12.5
E: MOTOR
E parameters
cover drive input voltage, V/f pattern, and motor parameters.
◆
E1: V/F PARAMETER MOTOR 1
E1 parameters
are used to set the drive input voltage and motor V/f characteristics. To switch drive operation
from one motor to another motor, set the V/f characteristics for motor 1.
■
V/f Pattern Settings
The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference.
This product has been preconfigured with 15 voltage/frequency (V/f) patterns. Use
E1-03 [V/f Pattern Selection]
to select the V/f pattern that is appropriate for the application.
Additionally, one custom V/f pattern is available. Set
E1-03 = F [Custom]
and then manually set parameters
E1-
04 to E1-10
.
Table 12.27 Predefined V/f Patterns
Setting
Specification
Characteristic
Application
0
Const Trq, 50Hz base, 50Hz max
Constant torque
For general purpose applications. This pattern is used when the load torque is constant without
any rotation speed such as that used for linear conveyor systems.
1
Const Trq, 60Hz base, 60Hz max
2
Const Trq, 50Hz base, 60Hz max
3
Const Trq, 60Hz base, 72Hz max
4
VT, 50Hz, 65% Vmid reduction
Variable torque
This pattern is used for torque loads proportional to 2 or 3 times the rotation speed, such as is
the case with fans and pumps.
5
VT, 50Hz, 50% Vmid reduction
6
VT, 60Hz, 65% Vmid reduction
7
VT, 60Hz, 50% Vmid reduction
8
High Trq, 50Hz, 25% Vmin boost
High starting torque
This pattern is used when strong torque is required during startup.
9
High Trq, 50Hz, 65% Vmin boost
A
High Trq, 60Hz, 25% Vmin boost
B
High Trq, 60Hz, 65% Vmin boost
C
High Freq, 60Hz base, 90Hz max
Constant output
This pattern is used to rotate motors at greater than 60 Hz. Output voltage is constant when
operating at greater than 60 Hz.
D
High Freq, 60Hz base, 120Hz max
E
High Freq, 60Hz base, 180Hz max
F
Custom
Constant torque
Enables a custom V/f pattern by changing
E1-04 to E1-13 [V/f Pattern for Motor 1]
. The
default settings for
E1-04 to E1-13
are equivalent to
Setting Value 1 [Const Trq, 60Hz base,
60Hz max]
.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...