SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
801
•
Output current is a minimum of 100% of the drive rated current and the frequency reference is less than 6 Hz.
•
Output current is a minimum of 109% of the drive rated current, the drive is in Normal Duty mode, and the
frequency reference is 7 Hz or more.
•
Output current is a minimum of 112% of the drive rated current, the drive is in Heavy Duty mode, and the
frequency reference is 7 Hz or more.
When the drive switches the carrier frequency to the set value, it uses the delay time set in
L8-40 [Carrier Red
Off-Delay Time]
and a hysteresis of 12%.
■
L8-40 Carrier Red Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-40
(04F1)
Carrier Red Off-Delay Time
Sets the length of time until the automatically reduced carrier frequency returns to the condition
before the reduction.
Determined by A1-02
(0.00 - 2.00 s)
Set
L8-40 ≠ 0.00
to enable the carrier frequency reduction function during start-up. When operation starts, the
drive automatically decreases the carrier frequency. When the time set in
L8-40
is expired, the carrier frequency
returns to the value set in
C6-02 [Carrier Frequency Selection]
.
When
L8-38 ≠ 1 [Carrier Reduction Mode = Enabled]
, the drive applies
L8-40
as the time for the carrier
frequency to return to its configured value after it is decreased.
■
L8-41 HCA alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-41
(04F2)
HCA alarm Selection
Sets the function to cause an
HCA [Current Alarm]
when the output current is more than 150% of
the drive rated current.
0
(0, 1)
0 : Disabled
The drive will not detect
HCA [Current Alarm]
.
1 : Enabled
If the output current is more than 150% of the drive rated current, the drive will detect
HCA
.
The MFDO terminal set for an alarm
[H2-01 to H2-03 = 4]
activates.
■
L8-51 STPo Current Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-51
(0471)
Expert
STPo Current Level
Sets the
STPo [Desynchronization Error]
detection level as a percentage of the output current.
0.0%
(0.0 - 300.0%)
The detection level is automatically calculated when
L8-51 = 0
.
■
L8-52 STPo Integral Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-52
(0472)
Expert
STPo Integral Level
Sets the detection level for
STPo [Desynchronization Error]
related to the ACR integral value.
1.0
(0.1 - 2.0)
■
L8-53 STPo Integral Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-53
(0473)
Expert
STPo Integral Time
Sets the length of time until the drive detects
STPo
after exceeding the value of
L8-51 [STPo
Current Level]
.
1.0 s
(1.0 - 10.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...