SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
■
F1-01 Enc1 Pulse Count (PPR)
No.
(Hex.)
Name
Description
Default
(Range)
F1-01
(0380)
Enc1 Pulse Count (PPR)
Sets the number of output pulses for each motor revolution.
1024 ppr
(1 - 60000 ppr)
■
F1-02 PGOpen Detection Select
No.
(Hex.)
Name
Description
Default
(Range)
F1-02
(0381)
PGOpen Detection Select
Sets the method to stop the motor or let the motor continue operating when the drive detects a
PGo [Encoder (PG) Feedback Loss]
.
1
(0 - 4)
When the drive does not detect ouput pulses from the encoder for the time set in
F1-14 [Enc PGOpen Time for
Detection]
, it will trigger
PGo
.
Note:
•
Motor speed and load conditions can cause
ov [Overvoltage]
and
oC [Overcurrent]
faults.
•
In AOLV control, set
n4-72 = 2 [Spd Fbk Mode = With PG]
.
0 : Ramp->Stop
The drive ramps to stop in the set deceleration time. Fault relay output terminal 1NO-1CM activates and terminal
1NC-1CM deactivates.
1 : Coast->Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal 1NO-1CM activates and
terminal 1NC-1CM deactivates.
2 : Fast Stop (C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal 1NO-
1CM activates and terminal 1NC-1CM deactivates.
3 : Alarm Only
The keypad shows
PGo
and the drive continues operation. Only use this setting in special conditions to prevent
damage to the motor and machinery. The output terminal set for
Alarm [H2-01 to H2-03 = 4]
activates.
4 : No Alarm Display
The drive continues operation and does not show
PGo
on the keypad. Only use this setting in special conditions to
prevent damage to the motor and machinery.
■
F1-03 Overspeed Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
F1-03
(0382)
Overspeed Detection
Selection
Sets the method to stop the motor or let the motor continue operating when the drive detects a
oS
[Overspeed]
.
1
(0 - 3)
When the motor speed is more than the value set in
F1-08 [Overspeed Level]
for longer than the time set in
F1-09
[Overspeed Delay Time]
trigger
oS
.
0 : Ramp->Stop
The drive ramps to stop in the set deceleration time. Fault relay output terminal 1NO-1CM activates and terminal
1NC-1CM deactivates.
1 : Coast->Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal 1NO-1CM activates and
terminal 1NC-1CM deactivates.
2 : Fast Stop (C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal 1NO-
1CM activates and terminal 1NC-1CM deactivates.
3 : Alarm Only
The keypad shows
oS
and the drive continues operation. Only use this setting in special conditions to prevent
damage to the motor and machinery. The output terminal set for
Alarm [H2-01 to H2-03 = 4]
activates.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...