SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
257
◆
Error Codes
■
Modbus Communications Error Code List
The following table lists the Modbus communications error codes.
When an error occurs, remove the cause of the error and restart communications.
Table 6.15 Modbus Communications Error Codes
Error Code
(Hex.)
Name
Cause
01
Function Code Error
The PLC set a function code that was not 03, 08, or 10 (Hex.)
02
Register Number Error
•
The register number that is trying to access is not registered.
•
A starting number that was not 0001 or 0002 (Hex.) was set when broadcasting.
03
Bit Count Error
•
Read and write data quantities are more than the 1 to 16 range. (Command message data quantity is disabled.)
•
The data that was read from non-consecutive holding registers contained more than 120 bytes.
•
The data to be written to non-consecutive holding registers contained more than 60 bytes.
•
In the write mode, the number of bytes in the message is not the number of data × 2.
21
Data Setting Error
•
Writing control data or parameters made the settings go out of the permitted setting range.
•
A parameter setting error occurred when writing a parameter.
22
Write Mode Error
•
Tried to write a disabled parameter during run.
•
When there was a
CPF06 [EEPROM Memory Data Error]
, the master tried to write a parameter other than one of these:
–
A1-00 [Language Selection]
–
A1-01 [Access Level]
–
A1-02 [Control Method]
–
A1-03 [Init Parameters]
–
A1-04 [Password Input]
–
A1-05 [Password Setting]
–
E1-03 [V/f Pattern Selection]
–
o2-04 [Drive KVA Selection]
•
Writes the read-only data.
23
DC Bus Undervoltage
Write Error
During
Uv [DC Bus Undervoltage]
, a
Uv
write disabled parameter was written.
24
Error Writing Data During
Parameter Processing
Tried to write a parameter from the master during parameter processing on the drive side.
25
Writing into EEPROM
Disabled
Writing into EEPROM write is disabled, but EEPROM write was executed from Modbus communications. When this error
occurs, the keypad shows a message and the drive continues operation.
■
No Response from Slave
The slave ignores the command message from the master and will not send a response message in these
conditions:
•
When a communications error (overrun, framing, parity, CRC-16) is detected in the command message.
•
When the slave address in the command message and the slave address for the drive side do not agree (Use
H5-
01 [Mbus Address]
to set the slave address of the drive)
•
When the time interval between the data of which the message is composed is longer than 24 bits
•
When the data length for the command message is not accurate
Note:
•
If the keypad shows
CALL [Serial Comm Transmission Error]
, refer to
“
Troubleshooting
”
to remove the cause of the error, and try to
do communications again. If the keypad does not show
CALL
, check
U1-19 [Modbus Err.Code]
for the error and error type.
•
If you execute the write function code when the slave address in the command message is 00 (Hex.), all of the slaves will execute the
write command, but they will not send response messages to the master.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...