496
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
No.
(Hex.)
Name
Description
MFAO Signal Level
Ref.
U4-11
(005D)
kWh Upper 5Digits
Shows the upper 5 digits of the watt hour value for the drive.
Unit: 1 MWh
Note:
Monitor
U4-11
shows the upper 5 digits and
U4-10 [kWh Lower 4Digits]
shows the
lower 4 digits.
Example for 12345678.9 kWh:
U4-10
: 678.9 kWh
U4-11
: 12345 MWh
No signal output
available
-
U4-13
(07CF)
Peak Hold Current
Shows the hold value of the peak value (rms) for the drive output current.
Use
U4-14 [PeakHold OutFreq]
to show the drive output frequency at the time that the
drive holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power
supply.
The drive keeps the held value during baseblock (during stop).
The keypad shows the value of
U4-13
in amperes (A). When looking at the monitor
through Modbus communications, the current is
“
8192 = drive rated current (A).
”
Calculate the current from the monitor value that is in at Modbus communications using
“
Numerals being displayed / 8192 × drive rated current (A).
Unit: Determined by the drive model.
•
0.01 A: 4002 to 4023
•
0.1 A: 4031 to 4675
No signal output
available
-
U4-14
(07D0)
PeakHold OutFreq
Displays the output frequency at which the peak value (rms) of the drive output current
is held.
The peak hold current can be monitored by
U4-13 [Peak Hold Current]
.
The peak hold output frequency will be cleared at the next startup and restart of the
power supply. The drive keeps the value that was under hold during baseblock (during
stop).
Unit: 0.01 Hz
No signal output
available
-
U4-16
(07D8)
MotorOLEstimate (oL1)
Shows the integrated value of
oL1 [Motor Overload]
as a percentage of
oL1
detection
level.
Unit: 0.1%
10 V: 100%
-
U4-18
(07DA)
FRef Source Selected
Shows the selected frequency reference source.
The keypad shows the frequency reference source as
“
XY-nn
”
as specified by these
rules:
X:
Ext Ref 1/2 [H1-xx = 9]
selection status
•
1:
b1-01 [Freq. Ref. Sel. 1]
•
2:
b1-15 [Freq. Ref. Sel. 2]
Y-nn: Frequency reference source
•
0-01: Keypad (
d1-01 [Reference 1]
)
•
1-00: Analog input (unassigned)
•
1-01: MFAI terminal AI1
•
1-02: MFAI terminal AI2
•
1-03: MFAI terminal AI3
•
2-02 to 2-17: Multi-step speed reference (
d1-02 to d1-17 [Reference 2 to Reference
16, and Jog Reference]
)
•
3-01: Modbus communications
•
4-01: Communication option card
•
5-01: Pulse train input
•
7-01: Q2pack
•
9-01: Up/Down command
No signal output
available
-
U4-19
(07DB)
Mbus FreqReference
Value
Shows the frequency reference sent to the drive from the Modbus communications as a
decimal.
Unit: 0.01%
No signal output
available
-
U4-20
(07DC)
Option FreqReference
Value
Shows the frequency reference sent to the drive from the communication option as a
decimal.
No signal output
available
-
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...