Parameter Setting Errors
Parameter setting errors occur when multiple parameter settings do not agree, or when parameter setting values
are not correct. Refer to the table in this section, examine the parameter setting that caused the error, and remove
the cause of the error. You must first correct the parameter setting errors before you can operate the drive. The
drive will not send notification signals for the faults and alarms when these parameter setting errors occur.
Code
Name
Causes
Possible Solutions
oPE01
Drive Capacity Setting Error
The value set in
o2-04 [Drive KVA Selection]
does
not agree with the drive model.
Set
o2-04
to the correct value.
Code
Name
Causes
Possible Solutions
oPE02
Parameter Range Setting Error
Parameters settings are not in the applicable setting
range.
1.
Push
to show
U1-18 [oPE Fault Parameter]
, and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
Set
E2-01 ≤ E2-03 [Mot Rated Current (FLA) ≤
Mot No-Load Current]
.
Make sure that
E2-01 > E2-03
.
Note:
If it is necessary to set
E2-01 < E2-03
, first lower the value
set in
E2-03
, and then set
E2-01
.
Code
Name
Causes
Possible Solutions
oPE03
Multi-Function Input Setting Err
The settings for these parameters do not agree:
•
Terminal DI1 to DI8 Function Selection
H1-01
to H1-08
•
Terminal D1 to DF Function Selection
F3-10 to
F3-25
•
Virtual Multi-Function Inputs 1 to 4
H7-01 to
H7-04
Set the parameters correctly.
The settings for the standby mode function do not
agree:
•
b8-50 = 0 [Standby Mode Selection = Disabled]
and
H2-xx: MFDO Function Select = C
[@Standby]
•
b8-50 = 1 [Enabled]
and
H2-xx ≠ C
Set the parameters correctly.
The settings for MFDIs overlap.
Note:
This does not include
H1-xx: MFDI Function
Select = 20 to 2F [External Fault]
and
[Reserved]
.
Set the parameters correctly to prevent MFDI function overlap.
These pairs of MFDI functions are not set to Digital
Inputs (
H1-xx
,
F3-10 to F3-25
, and
H7-01 to H7-
04
) at the same time:
•
Setting values
62 [Up Command]
and
63 [Down
Command]
•
Setting values
65 [Up2 Command]
and
66 [Dw2
Command]
•
Setting values
3 [Run Command]
and
4 [FWD/
REV Cmd]
Set the MFDI pairs.
A minimum of two of these MFDI combinations are
set to Digital Inputs (
H1-xx
,
F3-10 to F3-25
, and
H7-01 to H7-04
) at the same time:
•
Setting values
62 [Up Command]
and
63 [Down
Command]
•
Setting values
65 [Up2 Command]
and
66 [Dw2
Command]
•
Setting values
17 [Ac/Dec Hold]
•
Setting values
16 [Ref Sample]
•
Setting values
E to 10 [Add Offset Frequency 1
to 3 (d7-01 to d7-03)]
Remove the function settings that are not in use.
These PID settings are enabled at the same time.
•
b5-01 [PID Enable]
•
H1-xx = 62 [Up Command]
•
H1-xx = 63 [Down Command]
•
Set
b5-01 = 0 [Disabled]
.
•
Remove the function Up/Down command settings.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...