SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
277
Code
Name
Causes
Possible Solutions
oH4
Motor Overheat Fault (PTC Input)
The motor has overheated.
•
Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
•
Decrease the load.
•
Increase the values set in Acceleration/Deceleration Times
C1-
01 to C1-08
.
•
Set
E2-01 [Mot Rated Current (FLA)]
correctly to the value
specified by the motor nameplate.
•
Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
•
Adjust V/f Pattern Parameters
E1-04 to E1-10
. For motor 2,
adjust
E3-04 to E3-10
. Decrease the values set in
E1-08 [Mid
A Voltage]
and
E1-10 [Min Output Voltage]
.
Note:
If
E1-08
and
E1-10
are set too low, the overload tolerance will
decrease at low speeds.
Note:
•
The drive detects this fault if the motor overheat signal that was entered to an analog input terminals A1, A2, or A3 is more than the alarm detection level. (If
H3-02 [AI1
Function Selection], H3-10 [AI2 Function Selection], or H3-06 [AI3 Function Selection] = 16 [Mot PTC Input]
was set.)
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oL1
Motor Overload
The load is too heavy.
Decrease the load.
Note:
Reset
oL1
when
U4-16 [MotorOLEstimate (oL1)]
< 100.
The acceleration/deceleration times or cycle times
are too short.
•
Examine the acceleration/deceleration times and the motor
start/stop frequencies (cycle times).
•
Increase the value set in Acceleration/Deceleration Times
C1-
01 to C1-08
.
Overload occurred while running at low speed.
•
Lower the load when running at low speed.
•
Increase the motor speed.
•
If the motor is run frequently at low speeds, replace the motor
with a larger motor or use a drive-dedicated motor.
Note:
For general-purpose motors, overload can occur while
running at low speed when operating at below the rated
current.
L1-01 [Motor Cool Type for OL1 Calc]
is set
incorrectly.
Set
L1-01
in as specified by the motor qualities for a drive-
dedicated motor.
The V/f pattern does not fit the motor qualities.
•
Examine the ratios between the V/f pattern frequency and
voltage. Decrease the voltage if it is too high compared to the
frequency.
•
Adjust V/f Pattern Parameters
E1-04 to E1-10
. For motor 2,
adjust
E3-04 to E3-10
. Decrease the values set in
E1-08 [Mid
A Voltage]
and
E1-10 [Min Output Voltage]
.
Note:
If
E1-08
and
E1-10
are set too low, the overload tolerance will
decrease at low speeds.
E1-06 [Base Frequency]
is set incorrectly.
Set
E1-06
to the rated frequency shown on the motor nameplate.
One drive is operating more than one motor.
Set
L1-01 = 0 [Motor Cool Type for OL1 Calc = Disabled]
,
connect thermal overload relay to each motor to prevent damage
to the motor.
The electronic thermal protector qualities and the
motor overload properties do not match.
•
Examine the motor qualities and set
L1-01 [Motor Cool Type
for OL1 Calc]
correctly.
•
Connect a thermal overload relay to the motor.
The electronic thermal protector is operating at an
incorrect level.
Set
E2-01 [Mot Rated Current (FLA)]
to the value shown on the
motor nameplate.
There is increased motor loss from overexcitation
operation.
•
Lower the value set in
n3-13 [OverExcBr Gain]
.
•
Set
L3-50 ≠ 3 or 4 [StallP@Decel Mode ≠ HiFlux
Overexcitation or HiFlux2 Overexcitation]
.
•
Set
L3-04 = 0 [StallP@Decel Enable = Disabled]
.
The speed search-related parameters are set
incorrectly.
•
Examine the settings for all speed search related parameters.
•
Adjust
b3-03 [SpSrch Deceleration Time]
.
•
Set
b3-24 = 1 [SpSrch Method Selection = Speed Estimation]
after Auto-Tuning.
Phase loss in the input power supply is causing the
output current to change.
Make sure that there is no phase loss, and repair problems.
Note:
•
The drive detects this fault if the electronic thermal protector of the drive started the motor overload protection.
•
Do a Fault Reset to clear the fault.
•
L5-07 [OL1-4 Auto-Reset Select]
disables the Auto Restart function.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...