SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
663
Terminal V1 will output an analog signal = 100% of the parameter set in
F4-01
.
4. View the monitor connected to terminal V1 and adjust
F4-05
.
•
Use Gain and Bias to Adjust the Output Signal Level of Terminal V2
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the
F4-04 [Term.V2 Gain]
value on the keypad.
Terminal V2 will output a voltage = 100% of the monitor set in
F4-03 [Term.V2 Function Selection]
.
2. View the monitor connected to terminal V2 and adjust
F4-04
.
3. View the
F4-06 [Term.V2 Bias]
value on the keypad.
The analog signal equal to 0% of the parameter being set in
F4-03
will be output from terminal V2.
4. View the monitor connected to terminal V2 and adjust
F4-06
.
■
F4-01 Term.V1 Funct Selection
No.
(Hex.)
Name
Description
Default
(Range)
F4-01
(0391)
Term.V1 Funct Selection
Sets the monitor signal output from terminal V1.
102
(000 - 999)
Enter the last three digits of
Ux-xx [MONITORS]
to set monitor data to output from the option card. For example,
set
x-xx
to
102
to monitor
U1-02 [Output Frequency]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set
000
or
031
. You can use this setting to adjust the V1 terminal output from PLC
through Modbus communications or a communications option.
■
F4-02 Term.V1 Gain
No.
(Hex.)
Name
Description
Default
(Range)
F4-02
(0392)
RUN
Term.V1 Gain
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal output
level from the terminal V1 at 10 V or 20 mA as 100% when an output for monitoring items is
100%.
100.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use
F4-07 [Term.V1 Level of Signal]
to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V1 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V1
outputs a maximum voltage of 10 V.
•
F4-01 [Term.V1 Funct Selection] = 102 (U1-02: Output Frequency)
•
F4-02 = 50.0%
•
F4-05 [Term.V1 Bias] = 0.0%
•
F4-07 = 0 (0 to 10V)
■
F4-03 Term.V2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F4-03
(0393)
Term.V2 Function Selection
Sets the number for monitor item of output from terminal V2.
103
(000 - 999)
Enter the last three digits of
Ux-xx [MONITORS]
to set monitor data to output from the option card. For example,
set
x-xx
to
103
to monitor
U1-03 [Output Current]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set
000
or
031
. You can use this setting to adjust the V2 terminal output from PLC
through Modbus communications or a communications option.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...