10.2 Model Specifications (200 V Class)
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
363
10.2
Model Specifications (200 V Class)
Table 10.2 Rating (200 V Class)
Model
2004
2006
2010
2012
2018
2021
2030
2042
Maximum Applicable Motor
Output (kW)
0.55
0.75
1.5
2.2
3
4
5.5
7.5
0.75
1.1
2.2
3
4
5.5
7.5
11
Maximum Applicable Motor
Output (HP)
1/2
1
2
3
4
5
7 1/2
10
3/4
1 1/2
3
4
5
7 1/2
10
15
Input
Rated Input
Current (A)
HD1 (AC)
3.6
4.8
8.9
12.7
17
20.7
30
40.3
HD1 (DC)
4.5
5.9
11
16
21
25
37
49
ND1 (AC)
4.8
6.7
12.7
17
20.7
30
40.3
52
ND1 (DC)
5.9
8.2
16
21
25
37
49
71
Output
Rated Output
Capacity
(kVA)
1.2
1.9
3.0
4.2
5.3
6.7
9.5
12.6
1.3
2.3
3.7
4.6
6.7
8.0
11.4
16.0
Rated Output
Current (A)
HD1
3.2
5
8
11
14
17.5
25
33
ND1
3.5
6
9.6
12.2
17.5
21
30
42
Overload Tolerance
•
HD: 150% of the rated output current for 60 seconds The permitted frequency of overload is once every 10 minutes.
•
ND: 110% of the rated output current for 60 seconds The permitted frequency of overload is once every 10 minutes.
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier Frequency
HD1: 8 kHz without derating the drive capacity.
ND1: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output Voltage
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
•
Advanced Open Loop Vector Control (AOLV) and EZ Open Loop Vector Control (EZOLV): 120 Hz
•
Closed Loop V/f Control (CL-V/f), Closed Loop Vector Control (CLV), Advanced Open Loop Vector Control for PM
(AOLV/PM), and Closed Loop Vector Control for PM (CLV/PM): 400 Hz
•
V/f Control (V/f), Open Loop Vector Control (OLV), and Open Loop Vector Control for PM (OLV/PM): 590 Hz
Measures for
Harmonics
DC reactor
External options
Braking
Device
Braking Transistor
Standard internal characteristics
EMC Filter
EMC Filter
IEC61800-3, C2/C3
Factory option
•
Models 2xxxB: There is a category C3 EMC filter in the drive.
•
Models 2xxxC: There is a category C2 EMC filter in the drive.
Power Supply
Rated Voltage/Rated
Frequency
•
Three-phase AC power supply 200 V to 240 V at 50/60 Hz
•
DC power supply 270 V to 340 V
Permitted Voltage Fluctuation
-15% to +10%
Permitted Frequency
Fluctuation
±5%
Input Power
(kVA)
HD1
1.5
2.0
3.7
5.3
7.1
8.6
12.5
16.8
ND1
2.0
2.8
5.3
7.1
8.6
12.5
16.8
21.6
*1
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*3
The rated output capacity is calculated with a rated output voltage of 208 V.
*4
The rated output capacity is calculated with a rated output voltage of 220 V.
Table 10.3 Rating (200 V Class)
Model
2056
2070
2082
2110
2138
Maximum Applicable Motor Output (kW)
11
15
18.5
22
30
15
18.5
22
30
37
Maximum Applicable Motor Output (HP)
15
20
25
30
40
20
25
30
40
50
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...