16 - 96
16. INDEXER POSITIONING OPERATION
(3) Alarm history clear
The alarm history can be confirmed by using the MR Configurator. The servo amplifier stores last six
alarms from when its power is switched on first. To control alarms which will occur during operation, clear
the alarm history using parameter No.PC18 (alarm history clear) before starting operation. Clearing the
alarm history automatically returns to "
0".
This parameter is made valid by switching power off, then on after setting.
Parameter No.PC18
0 0 0
Alarm history clear
0: Invalid (not cleared)
1: Valid (cleared)
(4) Rough match output
Rough match (RXn2) is output when the command remaining distance reaches the value set in parameter
No.PC11 (rough match output range). The setting range is 0 to 65535 [pulse].
Servo motor
speed
ON
OFF
ON
OFF
Rough match
(RXn2)
In position (RXnC)
Command pulse
Actual servo motor speed
Command remaining distance [pulse]
set in parameter No.PC11