3 - 54
3. CC-LINK COMMUNICATION FUNCTIONS
(3) Remote register-based point table No. setting (incremental value command system)
The following program example is only applicable when two stations are occupied.
Operate the servo amplifier of station 2 with incremental values after specifying the point table No.5 in the
direct specification mode.
Preset "
0" in parameter No.PA01 and "
0" in parameter No.PA30.
Set data
Description
K5
Point table No. (decimal)
Execute positioning operation to the point table No.5 by turning on X20.
Checks data link status of station No.2.
Servo-on command (RY20)
Incremental value selection (RY4B)
Turns on position instruction demand (RY40).
Point table establishment time 4ms *1
Turns off position instruction demand (RY40).
In position
Operation
command
Automatic operation mode selection (RY26)
Position/speed specifying system selection
(RY4A)
Reads respond code (RWr6) to D2 when
Position command execution completion (RX40)
turns on.
Turns on forward rotation start command
(RY21).
Command request time 6ms *1
Turns off forward rotation start command
(RY21).
*1: This is when the high-speed timer limit is set to 1ms.
Setting time for the timer should be larger than the command processing
time or twice the link scan time whichever larger. When the setting time
is short, the command cannot be received properly.
Writes point table No.5 (K5) to RWw8.
Содержание Melservo-J3 Series MR-J3-B
Страница 19: ...10 MEMO ...
Страница 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Страница 61: ...2 6 2 INSTALLATION MEMO ...
Страница 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Страница 241: ...5 62 5 OPERATION MEMO ...
Страница 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Страница 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Страница 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Страница 793: ...App 38 APPENDIX MEMO ...
Страница 799: ...MEMO ...