6 - 40
6. PARAMETERS
No.
Symbol
Name and function
Initial
value
Unit
Setting
range
PD25
A8DT CC-Link communication error (A8D) detection time
Select "CC-Link communication error (A8D) detection delay" with parameter
No.PC50 to enable this parameter.
When parameter No.PC50 is set to "0000h", 10ms is set.
Set a value converted from decimal to hexadecimal.
The setting range is up to 1000ms. A value exceeding the setting range will
be limited within the range.
For example) If "03E8h" is set, 1000ms will be set.
The converted decimal value of "1388h" is 10000ms, but it is limited to
1000ms, which is the upper limit of the setting range.
0000h ms 0000h
to
03E8h
CAUTION
If not detecting CC-Link
communication error (A8D), use
the initial setting value for the
communication time-out
detection time. When you
change the setting value, do not
set an unnecessarily long time
period.
Doing so interferes swift stop
operation at an occurrence of
CC-Link communication error
(A8D).
This parameter is available with servo amplifiers with software version A8 or
later.
When this parameter is set using MR Configurator with software version C5
or earlier, the parameter name is not displayed. However, the setting value is
changeable. Follow the instructions in this Instruction Manual to set the
value.
PD26
For manufacturer setting
0064h
PD27
Do not change this value by any means.
0000h
PD28
0000h
PD29
0000h
PD30
0000h
Содержание Melservo-J3 Series MR-J3-B
Страница 19: ...10 MEMO ...
Страница 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Страница 61: ...2 6 2 INSTALLATION MEMO ...
Страница 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Страница 241: ...5 62 5 OPERATION MEMO ...
Страница 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Страница 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Страница 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Страница 793: ...App 38 APPENDIX MEMO ...
Страница 799: ...MEMO ...