14 - 33
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Connection of the regenerative option
POINT
When the MR-RB50 MR-RB51 MR-RB3M-4 MR-RB3G-4 MR-RB5G-4
MR-RB34-4 MR-RB54-4 is used, a cooling fan is required to cool it. The
cooling fan should be prepared by the customer.
For the sizes of wires used for wiring, refer to section 14.9.
The regenerative option will cause a temperature rise of
100 relative to the ambient temperature. Fully
examine heat dissipation, installation position, used cables, etc. before installing the option. For wiring, use
flame-resistant cables and keep them clear of the regenerative option body. Always use twisted wires of
max. 5m length for connection with the servo amplifier.
(a) MR-J3-350T or less MR-J3-200T4 or less
Always remove the wiring from across P-D and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is disconnected when the regenerative option
overheats abnormally.
D
P
C
C
P
Servo amplifier
Regenerative option
Always remove the lead from across P-D.
G4
G3
(Note 2)
5m or less
Cooling fan (Note 1)
Note 1. When using the MR-RB50, MR-RB3M-4, MR-RB3G-4 or MR-RB5G-4, forcibly cool it with
a cooling fan (92 92, minimum air flow : 1.0m
3
).
2. Make up a sequence which will switch off the magnetic contactor when abnormal heating
occurs.
G3-G4 contact specifications
Maximum voltage: 120VAC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
Содержание Melservo-J3 Series MR-J3-B
Страница 19: ...10 MEMO ...
Страница 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Страница 61: ...2 6 2 INSTALLATION MEMO ...
Страница 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Страница 241: ...5 62 5 OPERATION MEMO ...
Страница 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Страница 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Страница 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Страница 793: ...App 38 APPENDIX MEMO ...
Страница 799: ...MEMO ...