1126800
SmartPAC 2 with WPC Integration
Page 140
Chapter 2
Installing SmartPAC 2 and WPC
Shadow Light Curtain Test
WPC tests whether your Shadow(s) are working properly by momentarily de-energizing the
Shadow transmitter whenever the press is started and stopped. WPC also ensures that the
Emergency stop relays are open.
WARNING
!
ELECTRIC SHOCK HAZARD WHEN WORKING INSIDE ENCLOSURE WITH POWER ON
•
DO NOT touch electrical connections or circuit boards.
•
Use test equipment only on the terminals specified in the instructions.
•
Ensure that this test is performed by qualified personnel.
Failure to comply with these instructions could result in death or serious injury.
Perform this test to verify that your Shadow V or Shadow VI light curtain is wired and
installed correctly and operating properly. If you have more than one light curtain on your
press, perform this test on each light curtain.
1. Power up the light curtain. Look at the Shadow transmitter to see if the amber (power-on)
indicator is illuminated.
•
If the transmitter’s amber indicator is lit, go to step 2.
•
If the transmitter’s amber indicator is not lit, power down the light curtain, check the
wiring to the transmitter and check the power fuse (in the receiver for Shadow V, in
the control box for the Shadow VI) and replace if necessary. Power up again. If the
amber indicator is still off, power down the transmitter and replace the indicator.
Power up again. If the amber indicator is still not lit, contact Wintriss Tech Support.
2. At the Shadow receiver, see if the green (curtain clear) indicator is lit.
•
If the receiver’s green indicator is lit, go to step 3.
•
If the receiver’s red indicator is lit, realign the light curtain heads. If the receiver’s red
indicator is still lit, check the interrupt circuit. The following terminal on your unit
should read 0 (zero) volts relative to ground:
Shadow V: INT terminal in the transmitter
Shadow VI: pin #19 on TB4 in the control
Shadow VI – WPC Interface Board: pin #5 on TB4
If the terminal does not read 0 (zero) volts relative to ground, check and correct the
ground wiring for the unit. If this does not cause the green indicator to come on,
contact Wintriss Tech Support.
•
If neither the receiver’s green nor red indicator is lit, power down the unit and check
the wiring to the receiver. Also check the power fuse (in the receiver for Shadow V,
in the control box for the Shadow VI), and replace if necessary. Power up again. If
Содержание SmartPAC 2
Страница 192: ...1126800 SmartPAC 2 with WPC Integration Page 170 Chapter 2 Installing SmartPAC 2 and WPC ...
Страница 222: ...1126800 SmartPAC 2 with WPC Integration Page 200 Chapter 3 SmartPAC 2 Keyboard Displays and Operating Modes ...
Страница 294: ...1126800 SmartPAC 2 with WPC Integration Page 272 Chapter 4 SmartPAC 2 Initialization Mode ...
Страница 342: ...1126800 SmartPAC 2 with WPC Integration page 320 Chapter 5 SmartPAC 2 Program Mode ...
Страница 404: ...1126800 SmartPAC 2 with WPC Integration Page 382 Chapter 6 SmartPAC 2 Run Mode ...
Страница 448: ...1126800 SmartPAC 2 with WPC Integration Page 426 Chapter 7 SmartPAC 2 Fault Messages ...
Страница 476: ...1126800 SmartPAC 2 with WPC Integration page 454 Appendix C Updating SmartPAC 2 Firmware ...
Страница 478: ...1126800 SmartPAC 2 with WPC Integration page 456 Appendix D SmartView Remote Viewing and E mail Setup ...
Страница 480: ...1126800 SmartPAC 2 with WPC Integration page 458 Appendix E Upgrade from Original SmartPAC to SmartPAC 2 ...
Страница 482: ...1126800 SmartPAC 2 with WPC Integration page 460 Appendix F Replacing SmartPAC 2 PC Board ...
Страница 492: ...1126800 SmartPAC 2 with WPC Integration page 470 Glossary ...