A - SW (ON)
B - Screw (OFF)
Figure 11.12 EMC Filter Switch Location 6
A - SW (ON)
B - Screw (OFF)
Figure 11.13 EMC Filter Switch Location 7
If you lose an EMC filter switch screw, use
to find the correct replacement screw and install the new
screws with the correct tightening torque.
NOTICE:
Only use the screws specified in this manual. If you use screws that are not approved, it can cause damage to the drive.
Table 11.4 Screw Sizes and Tightening Torques
Bypass Model
Drive Model
Screw Size
Tightening Torque
N
∙
m
D002 - D059
A002 - A054
B001 - B065
2011 - 2059, 4005 - 4065
M4 × 20
1.0 - 1.3
D074
A068
B077
2075 , 4077
M4 × 30
1.0 - 1.3