When reverse operation is prohibited, the drive will not accept a Reverse operation command.
0 : Reverse Enabled
The drive will accept a Reverse operation command.
1 : Reverse Disabled
The drive will not accept a Reverse operation command.
■
b1-08: Run Command Select in PRG Mode
No.
(Hex.)
Name
Description
Default
(Range)
b1-08
(0187)
Run Command Select in
PRG Mode
Sets the conditions for the drive to accept a Run command entered from an external source when
using the keypad to set parameters.
0
(0 - 2)
As a safety precaution, when the drive is in Programming Mode, it will not respond to a Run command.
This parameter helps prevent accidents that can occur if the motor starts to rotate because the drive received a Run
command from an external source while the user is programming the drive. You can also set the drive to not show the
Programming Mode when a Run command is active.
Note:
Refer to this table for Drive Mode and Programming Mode functions.
Mode
Keypad Screen
Function
Drive Mode
Monitors
Sets monitor display.
Programming Mode
Parameters
Changes parameter settings.
User Custom Parameters
Shows the User Parameters.
Parameter Backup/Restore
Saves parameters to the keypad as backup.
Modified Parameters/Fault Log
Shows modified parameters and fault history.
Auto-Tuning
Auto-Tunes the drive.
Initial Setup
Changes initial settings.
Diagnostic Tools
Sets data logs and backlight.
0 : Disregard RUN while Programming
The drive rejects the Run command while in Programming Mode.
1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source while in Programming Mode.
2 : Allow Programming Only at Stop
The drive does not let the user enter Programming Mode when the drive is operating. The drive does not show the
Programming Mode when a Run command is active.
■
b1-11: Run Delay @ Stop
No.
(Hex.)
Name
Description
Default
(Range)
b1-11
(01DF)
Run Delay @ Stop
Sets the amount of time that the drive will not accept the Run command again after the Run
command is lost.
0.0 s
(0.0 - 6000.0 s)
Note:
•
This parameter will operate for both AUTO Mode and HAND Mode.
•
This parameter will operate when the drive goes to sleep then wakes up.
•
The time set in this parameter does not apply for faults or Auto-Restarts.
•
When there is an active Run command while the time set in
b1-11
is active, the keypad will show a
[Start Delay]
message as specified by
the
o1-82 [Message Screen Display]
display format.
Coast to Stop with Timer Function
When
b1-03 = 3 [Stopping Method Selection = Coast to Stop with Timer]
, the drive operates as:
1. The drive operates at an output frequency > 0.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...