618
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Setting Value
Function
Description
Ref.
46
Add Offset Frequency 3
(d7-03)
Sets the function to add the offset frequency set in
d7-03 [Offset Frequency 3]
to the frequency reference when the
terminal activates.
51
Sequence Timer Disable
Sets the command to disable Sequence Timers.
ON : Sequence Timer is Disabled
52
Sequence Timer Cancel
Sets the command to cancel the currently active Sequence Timer.
ON : Cancel Active Sequence Timer
61
Speed Search from Fmax
Sets the function to start speed search using an external reference although
b3-01 = 0 [Speed Search Selection at Start
= Disabled]
.
Note:
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
62
Speed Search from Fref
Sets the function to use an external reference to start speed search although
b3-01 = 0 [Speed Search Selection at Start
= Disabled]
.
Note:
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
63
Field Weakening
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in
d6-01
[Field Weakening Level] and d6-02 [Field Weakening Frequency Limit]
when the input terminal is activated.
68
High Slip Braking (HSB)
Activate
Sets the command to use high-slip braking to stop the motor.
6A
Drive Enable
Sets the function to show
dnE [Drive Enabled]
on the keypad and ignore Run commands when the terminal is OFF.
70
Drive Enable 2
Sets the function to show
dnE [Drive Enabled]
on the keypad and ignore Run commands when the terminal is OFF.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to
b1-03
setting.
82
PI Switch to Aux
Sets
YF-xx [PI Auxiliary Control]
parameters as primary PI loop parameters and disables
b5-xx [PID Control]
.
Note:
When this input is active,
YF-xx [PI Auxiliary Control]
parameters will always be the primary PI loop parameters.
Parameter
YF-20 [PI Aux Main PI Speed Control]
does not have an effect.
83
Dedicated Multi-Setpoint
YA-02
Sets the function to set the PID setpoint to
YA-02 [Setpoint 2]
.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive
will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-02
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-03 [Setpoint 3]
, or
YA-04 [Setpoint 4]
is PID setpoint.
84
Dedicated Multi-Setpoint
YA-03
Sets the function to set the PID setpoint to
YA-03 [Setpoint 3]
. Set this function and
H1-xx = 83 [Dedicated Multi-
Setpoint YA-02]
at the same time.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive
will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-03
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-02 [Setpoint 2]
, or
YA-04 [Setpoint 4]
is PID setpoint.
85
Dedicated Multi-Setpoint
YA-04
Sets the function to set the PID setpoint to
YA-04 [Setpoint 4]
. Set this function,
H1-xx = 83 [Dedicated Multi-Setpoint
YA-02]
, and
H1-xx = 84 [Dedicated Multi-Setpoint YA-03]
at the same time.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive
will detect an
oPE03 [Multi-Function Input Setting Err]
.
ON :
YA-04
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-02 [Setpoint 2]
, or
YA-03 [Setpoint 3]
is PID setpoint.
88
Thermostat Fault
Sets the drive to show the
VLTS [Thermostat Fault]
when the input terminal is ON.
Note:
This function is active when the drive is running.
A8
PI2 Control Disable
Sets the command to disable the PI2 Control function. Parameter
S3-12 [PI2 Control Disable Mode Sel]
sets the
output performance.
ON : Enabled
OFF : Disabled
AA
PI2 Control Inverse
Operation
Sets the command to change the sign of the PI2 Control input.
AB
PI2 Control Integral Reset Sets the command to reset the PI2 Control integral value.
Note:
This input has priority over
H1-xx = AC [MFDI Function Selection = PI2 Control Integral Hold]
.
AC
PI2 Control Integral Hold Sets the command to lock the PI2 Control integral value.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...