10.6 MEMOBUS/Modbus Communications
758
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Register No.
(Hex.)
Description
0038
PID Feedback: Unsigned, input is equivalent to 100%/maximum output frequency (Units: 0.1%)
0039
PID Input: Signed, ±100%/±maximum output frequency (Units: 0.1%)
003A
PID Output: Signed, ±100%/±maximum output frequency (Units: 0.1%)
003B - 003C
Reserved
003D
Bypass serial communications error description
Note:
The drive saves the description of the communications error until you reset the fault.
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 - F
Reserved
003E
Output Frequency
Units: min
-1
or r/min
Note:
Set
E2-04 [Motor Pole Count]
.
003F
0.01% units
0040 - 004A
Used with
U1-xx [Operation Status Monitors]
. Refer to the
U Monitor
for parameter details.
004B
U1-12 [Drive Status]
bit 0
1: During Run
bit 1
1: During zero speed
bit 2
1: During reverse
bit 3
1: During reset signal input
bit 4
1: During speed agreement
bit 5
1: Drive operation ready
bit 6
1: Minor Fault
bit 7
1: Fault
bit 8
1: oPExx [Operation Error] generation
bit 9
1: Recovery from momentary power loss, 0: Power recovery
bit A
1: Motor 2 Selection
bit B
Reserved
bit C
1: AUTO Mode
bit D
1: HAND Mode
bit E
1: ComRef status/ NetRef status
bit F
1: ComCtrl status/ NetCtrl status
004C - 007E
Use with
U1-xx, U4-xx, U5-xx, U6-xx [Monitors]
. Refer to
“
U2: Fault Trace
”
and
“
U3: Fault History
”
for more information.
007F
Minor Fault Code. Refer to
for more information.
0080 - 0097
Use with
U2-xx, U3-xx [Monitors]
. Refer to
“
U Monitor
”
for more information, and refer to
“
Fault Trace/Fault History Descriptions
”
for more information about
register values.
0098 - 0099
U4-01 [Cumulative Ope Time]
Example: When
U4-01 [Cumulative Ope Time]
is 12345, 0098 (Hex.) = 1234 and 0099 (Hex.) = 5.
009A - 009B
U4-03 [Cooling Fan Ope Time]
Example: When
U4-03 [Cooling Fan Ope Time]
is 12345, 009A (Hex.) = 1234 and 009B (Hex.) = 5.
009C - 00AA
Reserved
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...