YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
87
Table 3.10 Output and Control Wiring
Model
H6BP
Motor Wiring
Standard Motor
Terminal Block TB1
Ground Wiring
Control Wiring
AWG,
kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
A1
Terminal Blocks
TB1, TB3-TB6
A1
Terminal Block
TB2 (FE)
A2
Terminal Blocks
TB1-TB4 and TB6
Panel
Terminal Block
TB4
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
B001
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B002
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B003
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B004
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B007
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B011
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B014
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B021
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B027
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B034
14-2
32
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B040
14-2
32
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B052
14-2
32
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B065
14-2
32
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B077
6-2/0
120
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
B096
14 - 8 or
6 - 2/0
50 or 120
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
B124
(1-2) x
(6) or (4)
or (3 - 4/
0)
(1-2) x 80
or 100 or
150
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
B156
6 - 350
kcmil
275
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
B180
6 - 350
kcmil
275
14 - 2/0
120
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
B240
(1-2) x (4
- 500
kcmil)
(1-2) x 500
14 - 2/0
120
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
B302
(1-2) x (4
- 500
kcmil)
(1-2) x 500
14 - 2/0
120
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
*1
24-16 is acceptable for solid wire or ferrule use only.
◆
Main Circuit Terminal and Motor Wiring
This section outlines the various steps, precautions, and checkpoints to wire the main circuit terminals and motor
terminals.
WARNING!
Fire Hazard. Do not connect main power supply wiring to motor terminals U/T1, V/T2, and W/T3. Connect main power
supply wiring to main circuit input terminals R/L1, S/L2, and T/L3. Incorrect wiring can cause serious injury or death from fire.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...