5.10 o: Keypad-Related Settings
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
369
Sets the display of the time shown in the upper-left of the HOA keypad screen.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
■
o4-23: Date Format
No.
(Hex.)
Name
Description
Default
(Range)
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available on an HOA keypad.
2
(0 - 2)
Sets the date format that the drive uses for the fault history and other records.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
Note:
The Fault History in the Monitor Mode shows when faults occurred. Refer to
Show Fault History on page 153
for more information.
■
o4-24: bAT Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-24
(310F)
RUN
bAT Detection Selection
Sets operation when the drive detects
bAT [Keypad Battery Low Voltage]
and
TiM [Keypad Time Not
Set]
.
0
(0 - 2)
0 : Disable
The drive will not detect
bAT
or
TiM
.
1 : Enable (Alarm Detected)
TiM
or
bAT
shows on the keypad, and operation continues. The output terminal set for Alarm
[H2-01
to
H2-03 = 10]
activates.
2 : Enable (Fault Detected)
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC activates, and MB-MC
deactivates.
◆
o5: Log Function
The data log function saves drive status information as a CSV file in the microSD memory card in the keypad.
Monitors Ux-xx
are the source of data log information. You can record a maximum of 10 monitors.
Change the HOA keypad screen from the main menu to the Diagnostic Tools screen and select the data log function.
Set the number of the monitor to record and the sampling time, then start to record the data log.
Table 5.52 Setting Parameters for Data Log Items
No.
Name
Default
Data Log Monitors
o5-03
Log Monitor Data 1
101
U1-01 [Frequency Reference]
o5-04
Log Monitor Data 2
102
U1-02 [Output Frequency]
o5-05
Log Monitor Data 3
103
U1-03 [Output Current]
o5-06
Log Monitor Data 4
107
U1-07 [DC Bus Voltage]
o5-07
Log Monitor Data 5
108
U1-08 [Output Power]
o5-08
Log Monitor Data 6
000
Not selected
o5-09
Log Monitor Data 7
000
Not selected
o5-10
Log Monitor Data 8
000
Not selected
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...