188
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
•
Current Input
Refer to
to use a current signal input to one of the MFAI terminals.
Table 5.19 Frequency Reference Current Input
Terminal
Signal Level
Parameter Settings
Note
Signal Level Selection
Gain
Bias
Bypass MFAI
4 - 20 mA
Z2-30 = 2
Z2-32
Z2-33
Set Jumper Switch S2 to
“
I
”
for current
input.
0 - 20 mA
Z2-30 = 3
Figure 5.2 Example of Setting the Frequency Reference with a Current Signal to the Bypass MFAI
Changing between Master and Auxiliary Frequency References
2 : Serial Communications
The bypass uses serial communications to enter the frequency reference.
3 : Option PCB
The bypass uses a communications option card or input option card connected to the bypass control board to enter the
Run command.
Note:
If
b1-01 = 3
, but you did not connect a communications option card,
oPE05 [Run Cmd/Freq Ref Source Sel Err]
will flash on the keypad.
■
b1-02: Run Command Selection 1
No.
(Hex.)
Name
Description
Default
(Range)
b1-02
(0181)
Run Command Selection 1
Sets the input method for the Run command.
7
(0 - 9)
0 : Keypad
The bypass uses the keypad to enter the Run command.
Note:
The
on the keypad is on while keypad is the Run command source.
1 : Digital Input
The bypass uses the control circuit terminals to enter the Run command. Select the input method for the Run
command with an
Z2-xx
parameter.
Set
Z2-xx = 21, 37 [Run (AUTO), Run Reverse (AUTO)]
.
•
2-wire Sequence
When you set
A1-03 = 2220 [Initialize Parameters = 2-Wire Initialization]
, it will initialize the bypass and set
Z2-
01 = 21 [Run FWD]
. Run Reverse is not set by default.
2 : Serial Communications
The bypass uses serial communications to enter the Run command.
3 : Option PCB
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...