Figure 5.102 Run Delay with Preset Speed Example: Preset Speed with Run Delay
■
Z1-16 to Z1-25: Bypass Energy Savings
This feature helps you save energy and decrease harmonics by automatically switching to Bypass while in Drive
Mode.
You can use one of two methods with
Z1-16 [Energy Savings Mode]
to switch into Energy Savings:
Frequency Only
When
Z1-16 = 1 [Frequency]
, it will enable Energy Savings based on frequency only. The bypass will automatically
switch to Bypass when the unit meets these conditions for
Z1-22 [Energy Savings Mode Time]
:
•
Drive frequency reference is in
Z1-19 [Energy Savings Mode Frequency Reference Deadband]
of
Z1-17 [Energy
Savings Mode Frequency]
.
•
Drive output frequency is in
Z1-20 [Energy Savings Mode Output Frequency Deadband]
of
Z1-17 [Energy Savings
Mode Frequency]
.
Frequency and Output Current
When
Z1-16 = 2 [Fre Current]
, it will enable Energy Savings based on frequency and output current. The
bypass will automatically switch to Bypass when it meets the
Frequency Only
conditions and the drive output current
is in
Z1-21 [Energy Savings Mode Output Current Deadband]
of
Z1-18 [Energy Savings Mode Output Current
Level]
.
When the above conditions are met, the system:
1. Increases the drive frequency reference by the value in
Z1-23 [Energy Savings Mode Frequency Reference
Increase]
.
2. Waits for the drive output frequency to align with the frequency reference
3. Sets the drive to baseblock
4. Removes the effect of
Z1-23
from the drive frequency reference
5. Delays based on the time set to
L2-03 [Minimum Baseblock Time]
6. Opens drive output contactor K2
7. Delays based on the time set to
Z1-24 [Contactor Open Delay Time]
8. Closes Bypass contactor K3 and transfers to Bypass.
When the drive frequency reference is not in the
Z1-19 [Energy Savings Mode Frequency Reference Deadband]
of
Z1-17 [Energy Savings Mode Frequency]
, the system:
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 10.0 sec
Z1-13 Pre Interlock Run Select = 1 (Enable)
Z1-14 Run Delay Frequency Reference = 30.0 Hz
Z1-15 Interlck Wait Time = 0.0 sec (Never Time Out)
Z1-14 Run Delay Frequency Reference
Z1-12 Run Delay Time
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...