195
b1-11: Run Delay @ Stop
Figure 5.13 Run Delay Memory Running & Stop
■
b1-17: Run Command at Power Up
No.
(Hex.)
Name
Description
Default
(Range)
b1-17
(01C6)
Run Command at Power Up
Sets drive response when you apply power to drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run command.
1
(0, 1)
0 : Disregard Existing RUN Command
The drive does not start to operate the application when you apply power, even when there is an existing Run
command.
Enter the Run command again to operate the application.
Note:
When you energize the drive, if there is an existing Run command enabled from an external source,
on the keypad will flash quickly.
1 : Accept Existing RUN Command
When there is an existing Run command, the drive starts to operate the application when you apply power.
■
b1-40: Deceleration Abort Time
No.
(Hex.)
Name
Description
Default
(Range)
b1-40
(3BCF)
Deceleration Abort Time
Sets the maximum time until the drive shuts off the output to decelerate to stop.
0.0 s
(0.0 - 6000.0 s)
Note:
Set this parameter to 0.0 s to disable this function.
When
b1-40
> 0.0 s, the drive will coast-to-stop when you remove the Run command and decelerate for the time set
in
b1-40
. Refer to
for the timing chart.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...