10.5 Metasys N2 Communications
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
735
*1
Refer to
for
information on fault decimal values.
■
Metasys N2 Analog Output (AO) Summary
Table 10.16 Metasys N2 Analog Output Summary (Drive to Metasys N2)
Object ID
Object Name
Units
Default Value
Drive Parameters
AO 1
Speed Command
0.01 Hz
-
-
AO 2
Acceleration Time
s
30.0
C1-01
AO 3
Deceleration Time
s
30.0
C1-02
AO 4
PI Proportional Gain
-
2.00
b5-02
AO 5
PI Integral Time
s
5.0
b5-03
AO 6
Stall Prevention Level - Run
%
120
L3-06
AO 7
Stall Prevention Level - Accel
%
120
L3-02
AO 8
Reference Operation Mode Select
-
1
b1-01
AO 9
Run Operation Mode Select
-
1
b1-02
AO 10
PI Mode Select
-
0
b5-01
AO 11
Frequency Command Upper Limit
% of Max
100.0
d2-01
AO 12
Frequency Command Lower Limit
% of Max
0.0
d2-02
AO 13
Motor Rated Current
A
Motor model dependent
E2-01
AO 14
Jump Frequency 1
0.1 Hz
0.0
d3-01
AO 15
Jump Frequency 2
0.1 Hz
0.0
d3-02
AO 16
Jump Frequency 3
0.1 Hz
0.0
d3-03
AO 17
Jump Frequency Bandwidth
0.1 Hz
1.0
d3-04
AO 18
Number of Auto Restarts
-
0
L5-01
AO 19
Operator Display Mode
-
0
o1-03
AO 20
Power Loss Ride-Thru
s
Drive model dependent
L2-02
AO 21
Cable Loss Timeout
s
2.0
H5-09
AO 22
Cable Loss Speed
0.01 Hz
0.00
H5-34
AO 23
PI Integral Limit
0.1%
100.0
b5-04
AO 24
PI Upper Limit Value
0.1
100.0
b5-06
AO 25
PI Offset Adjustment
0.1
0.0
b5-07
AO 26
PI Primary Delay Time
0.01
0.00
b5-08
AO 27
Not Used
-
-
-
AO 28
Not Used
-
-
-
AO 29
Not Used
-
-
-
AO 30
Read Parameter Number
-
-
-
AO 31
Write Parameter Number
-
-
-
AO 32
Write Parameter Data
-
-
-
■
Metasys N2 Binary Input (BI) Summary
Table 10.17 Metasys N2 Binary Input Summary (Drive to Metasys N2)
Object ID
Object Name
Default
OFF (0) State
ON (1) State
BI 1
System Run/Stop Monitor
0
Stopped
Running
BI 2
System Forward/Reverse Monitor
0
Forward
Reverse
BI 3
System Ready Monitor
0
Not Ready
Ready
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...