Z3: Bypass Control Serial Comm
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
Z3-12
(850B)
Network Digital Inputs
Enables and disables control of the digital inputs over a network. It is not necessary to wire
to the physical digital input.
0 : Disabled
1 : Enabled
0
(0, 1)
Z3-13
(850C)
BACnet Register
Retention
Sets what to restore when you lose power then reapply power.
WARNING!
Sudden Movement Hazard. Clear all personnel from
the drive, motor, and machine area before you reapply power. If
you set this parameter to 2 or 3, the bypass unit can start before
it receives a valid network message. Failure to obey can cause
injury to personnel.
0 : Disabled
1 : Restore Frequency Reference Only
2 : Restore Commands Only
3 : Restore Commands and Freq Ref
0
(0 - 3)
Z3-16
(850F)
Apogee Run Enable
LDO35
This parameter is applicable only when
H5-08 = 2 [Communication Protocol Selection =
Apogee/P1]
.
Sets whether the data in point LDO 35 will have an effect on the ability of the bypass to
run.
0 : Disabled
1 : Enabled
0
(0, 1)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...