YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
629
Setting Value
Function
Description
Ref.
2D
Differential Level Source
Enters a feedback value to calculate the Differential Level between the
Differential Level Source
feedback and the
primary
PID Feedback [H3-xx = B]
.
Note:
The full-scale of the analog signal goes from
b5-71 [Min PID Transducer Scaling]
to
b5-38 [PID User Unit
Display Scaling]
.
2E
HAND Frequency Ref or
Setpoint
Enters the
S5-05 [HAND Frequency Reference]
value or the
S5-06 [HAND Setpoint]
value. When
S5-01 = 0 [HAND
Frequency Reference Source = HAND Analog Input]
and
S5-03 = 0 [HAND Mode PI Selection = Disabled]
, the drive
enters HAND Frequency Reference. When
b5-01 ≠ 0
,
S5-01 = 0
, and
S5-03 = 1 [Enabled]
, the drive enters HAND
Setpoint.
Note:
•
When PID is enabled, the full-scale of the analog signal goes from
b5-71 [Min PID Transducer Scaling]
to
b5-38
[PID User Unit Display Scaling]
.
•
When PID is disabled, the drive enters this analog signal as the percentage of the
E1-04 [Maximum Output
Frequency]
value.
◆
H4: Analog Outputs
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H4-01
(041D)
Terminal FM Analog
Output Select
Sets the monitor number to send from MFAO terminal FM.
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-01 = 102
to monitor
U1-02
[Output Frequency]
.
102
(000 - 999)
H4-02
(041E)
RUN
Terminal FM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
Sets the analog signal output level from the terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
H4-03
(041F)
RUN
Terminal FM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
Set the level of the analog signal sent from terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
H4-04
(0420)
Terminal AM Analog
Output Select
Sets the monitoring number to be output from the MFAO terminal AM.
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-04 = 103
to monitor
U1-03
[Output Current]
.
103
(000 - 999)
H4-05
(0421)
RUN
Terminal AM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 100%.
50.0%
(-999.9 - +999.9%)
H4-06
(0422)
RUN
Terminal AM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 0%.
0.0%
(-999.9 - +999.9%)
H4-07
(0423)
Terminal FM Signal
Level Select
Sets the MFAO terminal FM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
0
(0, 2)
H4-08
(0424)
Terminal AM Signal
Level Select
Sets the MFAO terminal AM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
0
(0, 2)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when you set
U1-08 [Output Power]
for analog output.
0.00 kW
(0.00 - 650.00 kW)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...