E2: Motor Parameters
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E2-01
(030E)
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
Determined by o2-04
(10% to 200% of the
drive rated current)
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
Determined by o2-04
(0.000 - 20.000 Hz)
E2-03
(0310)
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency and
the no-load voltage.
Determined by o2-04
(0 to E2-01)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 120)
E2-05
(0312)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
E2-06
(0313)
Motor Leakage
Inductance
Sets the voltage drop from motor leakage inductance when the motor is operating at the
rated frequency and rated current. This value is a percentage of Motor Rated Voltage.
Determined by o2-04
(0.0 - 60.0%)
E2-10
(0317)
Motor Iron Loss
Sets the motor iron loss.
Determined by o2-04
(0 - 65535 W)
E2-11
(0318)
Motor Rated Power
Sets the motor rated output in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by o2-04
(0.00 - 650.00 HP)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...