Note:
•
Parameter
YF-23 [PI Aux Ctrl Output Level Select]
sets the condition to wake up the drive.
–
YF-23 = 0 [Direct Acting]
: The PI Aux Feedback must be less than the level set in this parameter for longer than the time set in
YF-07
to
wake up.
–
YF-23 = 1 [Inverse Acting]
: The PI Aux Feedback must be more than the level set in this parameter for longer than the time set in
YF-07
[PI Aux Control Wake-up Time]
to wake up.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.
■
YF-07: PI Aux Control Wake-up Time
No.
(Hex.)
Name
Description
Default
(Range)
YF-07
(3F56)
PI Aux Control Wake-up
Time
Sets the time to wake up the drive when the drive after
YF-04 [PI Aux Control Minimum Level]
or
YF-24 [PI Auxiliary Ctrl Maximum Level]
put the drive to sleep.
1 s
(0 - 3600 s)
Note:
Parameter
YF-23 [PI Aux Ctrl Output Level Select]
sets the condition to wake up the drive.
•
YF-23 = 0 [Direct Acting]
: The PI Aux Feedback must be less than the level set in
YF-06
for longer than the time set in
YF-07
to wake up.
•
YF-23 = 1 [Inverse Acting]
: The PI Aux Feedback must be more than the level set in
YF-06 [PI Aux Control Wake-up Level]
for longer than
the time set in
YF-07
to wake up.
■
YF-08: PI Aux Control Minimum Speed
No.
(Hex.)
Name
Description
Default
(Range)
YF-08
(3F57)
RUN
PI Aux Control Minimum
Speed
Sets the minimum speed at which the drive can run when the PI Auxiliary Control has an effect on
the output speed.
0.00 Hz
(0.00 - 400.00 Hz)
Note:
The drive will use
Y1-06 [Minimum Speed]
and
Y4-12 [Thrust Frequency]
as the minimum speed when PI Aux Control does not have an
effect on the output speed or when you set
YF-08 < Y1-06 and Y4-12
.
■
YF-09: PI Aux Control Low Level Detect
No.
(Hex.)
Name
Description
Default
(Range)
YF-09
(3F58)
RUN
PI Aux Control Low Level
Detect
Sets the level below which the drive must be for longer than
YF-10 [PI Aux Control Low Lvl Det
Time]
to respond as specified by
YF-11 [PI Aux Control Low Level Det Sel]
.
0.0 PSI
(-999.9 - +999.9 PSI)
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameter
YF-10
only applies to when
YF-11 = 2 and 3 [Fault and Auto-Restart (time set by YF-15)]
.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.
■
YF-10: PI Aux Low Level Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
YF-10
(3F59)
RUN
PI Aux Low Level Detection
Time
Sets the length of time that the PI Aux Feedback must be less than
YF-09 [PI Aux Control Low Lvl
Detection]
to trigger a drive response when
YF-11 = 2 and 3 [PI Aux Control Low Level Det Sel =
Fault and Auto-Restart (time set by YF-15)]
.
0.1 s
(0.0 - 300.0 s)
■
YF-11: PI Aux Control Low Level Det Sel
No.
(Hex.)
Name
Description
Default
(Range)
YF-11
(3F5A)
PI Aux Control Low Level
Det Sel
Sets drive response when the PI Aux Feedback decreases to less than
YF-09 [PI Aux Control Low Lvl
Detection]
for longer than
YF-10 [PI Aux Control Low Lvl Det Time]
.
1
(0 - 3)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...