542
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
◆
480 V Models
Table 7.21 Drive Watt Loss (NEMA Rating)
Bypass Model
Drive Model
Rated Output
Current
A
Carrier Frequency
kHz
Interior Unit Loss
W
Cooling Fin Loss
W
Total Loss
W
B001 to B004
4005
4.8
5.0
36
39
75
B007
4008
7.6
5.0
45
63
108
B011
4011
11
5.0
56
142
198
B014
4014
14
5.0
66
196
262
B021
4021
21
5.0
89
212
301
B027
4027
27
5.0
112
285
397
B034
4034
34
5.0
128
327
455
B040
4040
40
5.0
145
373
518
B052
4052
52
5.0
178
470
648
B065
4065
65
5.0
224
600
824
B077
4077
77
5.0
271
819
1090
B096
4096
96
5.0
323
973
1295
B124
4124
124
5.0
423
1294
1717
B156
4156
156
5.0
332
1448
1780
B180
4180
180
5.0
395
1707
2102
B240
4240
240
5.0
406
1810
2216
B302
4302
302
5.0
866
2847
3712
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...