4.5 Automatic Parameter Settings Optimized for Specific Applications (Application Presets)
168
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
6.
Push
or
to select
A1-06
, then push
.
7.
Push
or
to change the value, then push
.
The parameter setting procedure is complete.
Note:
•
You cannot change the value set in
A1-06
. To select an application preset, first set
A1-03 = 2220
to initialize parameters and then make a
selection to
A1-06
. If initializing all parameters will cause a problem, it is not necessary to change settings.
•
When the drive changes to the
A1-06
setting, it will also reset the parameters automatically registered to
A2-17 to A2-32 [User Parameters
17 to 32]
when
A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms]
.