Code
Name
Causes
Possible Solutions
oPE10
V/f Data Setting Error
The parameters that set the V/f pattern do not satisfy
these conditions:
•
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
[Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Set the parameters correctly to satisfy the conditions.
Code
Name
Causes
Possible Solutions
oPE11
Carrier Frequency Setting Error
These parameters are set at the same time:
•
C6-05 > 6 [Carrier Freq Proportional Gain > 6]
•
C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When
C6-05 < 7
,
C6-04
becomes disabled.
C6-
03
stays active.
C6-02 to C6-05
settings are not in the applicable
setting range.
Set
C6-02 to C6-05
correctly.
Code
Name
Causes
Possible Solutions
oPE12
Incompatible Drive Software
This version of bypass software is not compatible
with the connected drive.
Flash the drive with compatible software.
Code
Name
Causes
Possible Solutions
oPE16
Energy Saving Constants Error
These parameters are set at the same time:
•
b8-01 = 1 [Energy Saving Control Selection =
Enabled]
•
S1-01 = 1 [Dynamic Noise Control = Enabled]
Disable Energy Saving Control or Dynamic Noise Control.
Code
Name
Causes
Possible Solutions
oPE29
Baud Rate Setting Error
The baud rate setting
[H5-02]
does not align with the
currently selected protocol
[H5-08]
.
One of these contradictory settings is true:
•
H5-08 = 1 and H5-02 ≠3 [Communication
Protocol Selection = Metasys/N2 and
Communication Speed Selection ≠ 9600 bps]
•
H5-08 = 2 and H5-02 ≠ 2, 3 [Communication
Protocol Selection = Apogee/P1 and
Communication Speed Selection ≠ 4800 bps, 9600
bps]
•
H5-08 = 3 and H5-02 ≠ 3, 4, 5, 7 [Communication
Protocol Selection = BACnet and Communication
Speed Selection ≠ 9600 bps, 19.2 kbps, 38.4 kbps,
76.8 kbps]
Correct the parameter settings.
Code
Name
Causes
Possible Solutions
oPE33
Digital Output Selection Error
These two parameters are set at the same time:
•
H2-60 ≠ F [Term M1-M2 Secondary Function ≠
Not Used]
•
H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-63 ≠ F [Term M3-M4 Secondary Function ≠
Not Used]
•
H2-02 = 1xx [Term M3-M4 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-66 ≠ F [Term M5-M6 Secondary Function ≠
Not Used]
•
H2-03 = 1xx [Term M5-M6 Function Selection =
Inverse output of xx]
Clear the
H2-01 to H2-03 = 1xx [Inverse output of xx]
settings.
Note:
It is not possible to set
H2-01 to H2-03 = 1xx [Inverse output of
xx]
when using output functions for logic operations (
H2-60,
H2-63, H2-66 ≠ F
).
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...