9.19 Defaults by Bypass and Drive Model
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
689
No.
Name
Unit
Default
-
Bypass
Model
-
D002
D003
D004
D007
D010
A002
A003
A004
A006
A009
D016
A015
D024
A022
D030
A028
D046
A042
D059
A054
D074
A068
D088
A080
o2-04
Drive
Model
(KVA)
Selection
Hex.
65
67
68
6A
6B
6D
6E
6F
E2-11
Motor
Rated
Power
HP
(kW)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
L2-04
Powerloss V/
f Recovery
Ramp Time
s
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.6
L2-05
Undervoltage
Detection Lvl
(Uv1)
-
190
190
190
190
190
190
190
190
L3-24
Motor Accel
Time for
Inertia Cal
s
0.145
0.154
0.168
0.175
0.265
0.244
0.317
0.355
L8-02
Overheat
Alarm Level
°C
95
95
125
125
125
125
115
115
L8-09
Output
Ground Fault
Detection
-
0
0
0
0
0
1
1
1
L8-35
Installation
Method
Selection
-
2
2
2
2
2
2
2
2
L8-38
Carrier
Frequency
Reduction
-
2
2
2
2
2
2
2
2
n1-01
Hunting
Prevention
Selection
-
1
1
1
1
1
1
1
1
n1-03
Hunting
Prevention
Time
Constant
ms
10
10
10
10
10
10
10
10
No.
Name
Unit
Default
-
Drive Model
-
D114
A104
D143
A130
D169
A154
D211
A192
D273
A248
o2-04
Drive Model (KVA)
Selection
Hex.
70
72
73
74
75
E2-11
Motor Rated
Power
HP
(kW)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
b3-04
V/f Gain during
Speed Search
%
80
80
80
80
80
b3-06
Speed Estimation
Current Level 1
-
0.5
0.5
0.5
0.5
0.7
b3-08
Speed Estimation
ACR P Gain
-
0.50
0.50
0.50
0.50
0.50
b3-11
Spd Est Method
Switch-over Level
%
5.0
5.0
5.0
5.0
5.0
b3-12
Speed Search
Current Deadband
-
2.5
2.5
2.5
2.5
2.5
b3-26
Direction
Determination Level
-
1000
1000
1000
1000
1000
b8-04
Energy Saving
Coefficient Value
-
46.27
38.16
35.78
31.35
23.10
C6-02
Carrier Frequency
Selection
-
2
2
2
2
2
E2-01
Motor Rated Current
(FLA)
A
114
143
169
211
273
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...